AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 324 of 485
Query Syntax
[SOURce:]PULSe:WIDTh:MAXimum?
Description
This command the returns maximum permissible set value for the
PULSE width.
Returned Data Format
<nr2>
Query Example
PULS:WIDT:MAX?
Query return values for MINimim, MAXimum and DEFault are dependent on
MODE and interdependent parameter value settings
Query Syntax
[SOURce:]PULSe:WIDTh:DEFault?
Description
This command returns the default set value for the PULSE width.
Returned Data Format
<nr2>
Query Example
PULS:WIDT:DEF?
Query return values for MINimim, MAXimum and DEFault are dependent on
MODE and interdependent parameter value settings
Command Syntax
[SOURce:]PULSe:MODE <nr2>, <opt>
Description
This command sets the pulse width in seconds.
Parameters
< 0 | PW | 1 | PD | 2 | WD >
Encoding:
0 | PW program pulse by period and width
1 | PD program pulse by period and duty cycle
2 | WD program pulse by width and duty cycle
Parameter Format
<nr1> or <cr>
Example
PULS:MODE WD
Query Format
[SOURce:]PULSe:MODE?
Returned Data Format
<nr1>
Query Example
PULS:MODE?
2
Query Syntax
[SOURce:]PULSe:MODE:CATalog?
Description
This command returns the available programming modes: "0,Period
and width,1,Period and duty cycle,2,Width and duty cycle".
Parameters
None
Returned Data Format
<cr>
Query Example
PULS:MODE:CAT?
0,Period and width,1,Period and duty cycle,2,Width and duty cycle
Command Syntax
[SOURce:]PULSe:RAMP <nr2>, <opt>
Description
This command sets the pulse ramp time in seconds.
Parameters
Ramp time, Option: < NORmal | SATurate >
Default is NORmal if optional second parameter is omitted.
Parameter Format
<nr2>, <cr>
Example
PULS:RAMP 0.2
Query Format
[SOURce:]PULSe:RAMP?
Returned Data Format
<nr2>
Query Example
PULS:RAMP?
0.2