6.4.1
Power On Settings
The AFX Series will normally power up with the last settings in effect at turn-off for units
with firmware revision 1.6.0 or higher. Older firmware units will come up with factory
default settings.
Starting from firmware revision 1.6.0, this behavior is determined by the the
“SOURce:INITial” command. This feature is active by default. This makes the AFX
“remember” all the settings after cycling power.
This mode can be disabled by using the remote control command:
SOURce:INITial 0
This setting is retained in non-volatile (FLASH) memory.
6.4.2
PROGRAM Output Parameters
Figure 6-2: PROGRAM Screen
The two data entry methods described apply to the parameters on the main PROGRAM
screen. This includes those shown in the table below.
PARAMETER
Range
Unit
Description
Frequency
15 - 1200
Hz
Output frequency
Phase
0.0 – 359.0
Degrees Phase angles for phase B and C
Voltage AC
0 – 300
V rms
AC output
Voltage DC
0 - 425
Vdc
DC output
Current limit
0 to Max
A rms
RMS Current Limit
Power limit
0 to Max
W
True Power Limit
kVA limit
0 to Max
VA
Apparent Power Limit
Table 6-2: Available Output Parameters on PROGRAM screen
Each screen has up to five soft keys on the right hand side of the display. These may change
as the selected parameter changes. To move between parameter fields in any screen, use