AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 283 of 485
Command Syntax
[SOURce:]WAVEFORM:SINEwave
Description
This command modifies the #1 Sinewave harmonic content to reduce
voltage distortion at lower frequencies (< 100Hz). It does so by
disabling the 3
rd
Harmonic component that is normally included to
improve voltage distortion at high frequencies. Turning this OFF (0) is
recommended for Harmonics and Flicker system applications at 50
and 60 Hz. For Avionics and Defense applications at 400Hz or higher,
this mode should re-enabled (1). Not that this setting is saved in non-
volatile memory and is retained between power on/off cycles of the
power source.
Parameters
<b>
Parameter Format
n/a
Example
SOUR:WAVEFORM:SINE 0
Query Format
SOURce:WAVEFORM:SINEwave?
Query Example
SOUR:WAVEFORM:SINE?
0
Command Syntax
[SOURce:]WAVEFORM:SMOOTHen <NUMBER>
Description
This command Sets the smoothing filter size that is applied to the
waveform, in sample counts. A value of 1 makes the filter have no
effect (Disabled) and the maximum value is 101. Only odd numbers
are considered. The type of filter used is a moving-average-filter, or
MAF.
The smoothing filter is used to reduce slew rates of waveform edges.
This is useful in certain applications to make the waveform
reproduction more consistent and reduce potential distortion due to
the sampling rate of the controller, especially when reproducing
waveforms at high frequency.
Parameters
NUMBER
Parameter Format
<nr1>
Example
WAVEFORM:SMOOTH 33
Query Format
[SOURce:]WAVEFORM:SMOOTHen?
Returned Data Format
<nr1>
Query Example
WAVEFORM:SMOOTH?
33
Содержание AFX Series