9 Troubleshooting
9-18
9
A.81
A.81: Backup Error
Display and Outputs
Note
OFF: Output transistor is OFF (alarm state).
Status and Remedy for Alarm
Alarm Outputs
Alarm Code Outputs
ALM Output
ALO1
ALO2
ALO3
OFF
OFF
OFF
OFF
Cause
Remedy
A
The following power supplies to the abso-
lute encoder all failed:
• +5 V supply (supplied from Servo Driver)
• Battery
Follow absolute encoder set–up procedure.
B
Absolute encoder malfunctioned.
Replace the Servomotor.
C
Circuit board (1PWB) is defective.
Replace the Servo Driver.
Pn002.2 = 0
Pn002.2 = 1
C
A, B, C
A, C
At power ON
At SENS_ON command