6 DeviceNet Communications
6.5.4 Set/Read Commands for Remote I/O Communications
6-38
6
Origin Setting Command (Command Code: 1011, B Hex)
When an absolute encoder is used, the Origin Setting Command sets the present position of
the Servomotor as the origin. This command is disabled when an incremental encoder is
used.
To use the Origin Setting Command, make the command code settings and then change the
Command Start Command from 0 to 1. There is no need to set the data area.
When the origin has been set, an offset value is set for parameter Pn809 (Absolute Position
Setting). This set value is cleared when the W-series Servo Driver control power supply is
turned OFF. After the Origin Setting Command has been executed, therefore, the parameter
must be stored in flash ROM by executing the
Unit Reset Command.
Table 6.17 Commands for Origin Setting Command
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
0
ALRST
STOP
0
0
SVON
C_STRT
1
0
B Hex
2
0
3
4
0
5
6
7
Table 6.18 Responses for Origin Setting Command
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
READY
PWRON
STOP_R
ALRM
WARN
SVON_R C_STRT_R
1
0
B Hex
2
0
3
4
0
5
6
7
Содержание OMNUC W R88A-NCW152-DRT
Страница 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Страница 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Страница 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Страница 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...
Страница 257: ...9 Troubleshooting 9 46 9...