6.5 Remote I/O Communications
6-35
6
Responses
Details on bytes 1 to 7 of the responses for set/read commands (MOD = 1) are shown below.
Parameter Read Command (Command Code: 1000, 8 Hex)
The Parameter Read Command reads parameters for the W-series Servo Driver and
DeviceNet Unit.
To use the Parameter Read Command, make the following settings and then change the
Command Start Command from 0 to 1.
• Command code
• Parameter number
Table 6.10 Responses for Set/Read Commands
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
READY
PWRON
ESTP_R
ALRM
WARN
SVON_R C_STRT_R
1
0
Command code
2
Command number
3
4
Response data
5
6
7
General
status
Table 6.11 Commands for Parameter Read Command
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
0
ALRST
ESTP
0
0
SVON
C_STRT
1
0
8 Hex
2
Parameter number
3
4
0
5
6
7
Table 6.12 Responses for Parameter Read Command
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
1
READY
PWRON
ESTP_R
ALRM
WARN
SVON_R C_STRT_R
1
0
8 Hex
2
Parameter number
3
4
Parameter data
5
6
7
Содержание OMNUC W R88A-NCW152-DRT
Страница 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Страница 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Страница 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Страница 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...
Страница 257: ...9 Troubleshooting 9 46 9...