5 Parameter Settings
5.2.4 Speed, Acceleration, and Deceleration Parameters
5-6
5
5.2.4 Speed, Acceleration, and Deceleration Parameters
A table of speed, acceleration, and deceleration parameters is shown below.
Note 1.
“Steps” means “command unit.” For command unit details, refer to
5.3.1 Unit Parameters
.
2.
If you set the command unit to 0.001 mm, 1,000 steps/min becomes mm/min.
Object
Attribute
No.
Name
Range
Units
Effective
Timing
Default
Value
Type
0x64
#51
Pn821
Speed
1 to 240,000
×
1,000 steps/min
Immediate
24,000
B
#52
Pn822
Acceleration Time
1 to 10,000
ms
Immediate
100
B
#53
Pn823
Deceleration Time
1 to 10,000
ms
Immediate
100
C
#54
Pn824
Switch Speed
1 to 240,000
×
1,000 steps/min
Immediate
12,000
C
#55
Pn825
Second Accelera-
tion/Deceleration
Time
1 to 10,000
ms
Immediate
200
B
#56
Pn826
Acceleration/Decel-
eration Type
0 to 3
−
Immediate
0
B
#57
Pn827
Interrupt Feeding
Speed
1 to 240,000
×
1,000 steps/min
Immediate
24,000
B
#58
Pn829
Filter Selection
0 to 3
−
Immediate
0
B
#59
Pn830
JOG Unit Selection
0, 1
−
Immediate
0
B
#60
Pn831
JOG Speed
1 to 240,000
×
1,000 steps/min
Immediate
24,000
B
#61
Pn832
JOG Acceleration
Time
1 to 10,000
ms
Immediate
100
B
#62
Pn833
JOG Deceleration
Time
1 to 10,000
ms
Immediate
100
C
#63
Pn834
JOG Switch Speed
1 to 240,000
×
1,000 steps/min
Immediate
12,000
C
#64
Pn835
JOG Second Accel-
eration/Decelera-
tion Time
1 to 10,000
ms
Immediate
200
C
#65
Pn836
JOG Acceleration/
Deceleration Type
0 to 3
−
Immediate
0
B
#70
Pn840
Time Constant for
Exponential Curve
4 to 1,000
ms
Immediate
25
C
#71
Pn841
Bias Speed
0 to 240,000
×
1,000 steps/min
Immediate
0
C
#72
Pn842
Time Constant of
Moving Average
4 to 1,000
ms
Immediate
25
C
#73
Pn843
Maximum Speed
1 to 240,000
×
1,000 steps/min
Immediate
24,000
B
#74
Pn844
Step Distance 1
0 to
99,999,999
Steps
Immediate
1
B
#75
Pn845
Step Distance 2
0 to
99,999,999
Steps
Immediate
10
B
#76
Pn846
Step Distance 3
0 to
99,999,999
Steps
Immediate
100
B
#77
Pn847
Step Distance 4
0 to
99,999,999
Steps
Immediate
1,000
B
Содержание OMNUC W R88A-NCW152-DRT
Страница 1: ...Cat No I538 E3 1 DeviceNet Option Unit OMNUC W Series Model R88A NCW152 DRT...
Страница 53: ...4 Connectors 4 5 3 DeviceNet Network Configuration Restrictions 4 22 4...
Страница 97: ...5 Parameter Settings 5 3 8 Notch Signal Output Positioning 5 44 5...
Страница 211: ...8 Servo Driver Settings 8 5 3 Absolute Encoder Multi turn Limit Setting 8 24 8...