Variable name
Meaning
Diagnosis/Statistics Log Busy
Global/local
Global
Function
TRUE while the diagnosis/statistics log operation is in progress.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
*1.
This system-defined variable was added for unit version 1.11 of the CPU Unit.
Variable name
_EC_StatisticsLogErr
Meaning
Diagnosis/Statistics Log Error
Global/local
Global
Function
TRUE when the diagnosis/statistics log failed to start or it is impossible to write into the log.
The value of this flag is determined when
_EC_StatisticsLogBusy
(Diagnosis/Statistics Log Busy) changes to
FALSE after the diagnosis/statistics log operation is started.
The error end is caused by the following.
•
Another records cannot be added in the log file because the capacity of the SD Memory Card is fully used.
•
The SD Memory Card is write-protected.
•
There is no SD Memory Card.
•
The function cannot be started because the value specified for
_EC_StatisticsLogCycleSec
(Diagnosis/Statis-
tics Log Cycle) is invalid.
Data type
BOOL
Range of values
TRUE or FALSE
R/W access
R
Retained
Not retained.
Network Publish
Published.
Usage in user pro-
gram
Possible.
Related in-
structions
---
*1.
This system-defined variable was added for unit version 1.11 of the CPU Unit.
7 System-defined Variables Related to the Built-in EtherCAT Port
7-19
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
7-1
System-defined V
ariables That Are Related to the Built-in EtherCA
T Port
7
7-1-3
EtherCA
T Master Function Module, Category Name: _EC
Содержание NJ101-10 Series
Страница 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 68: ...2 Part Names and Slave Settings 2 18 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Страница 279: ......