Examples of Finding Error Locations
Example 1: Network Configuration Where an EtherCAT Junction Slave Is Not Used
Network Configuration Diagram
IN
OUT
OUT
OUT
IN
IN
IN
OUT
(B)
(A)
NJ/NX-series CPU Unit
EtherCAT master
(C)
Slave
node address 64
Slave
node address 3
Slave
node address 4
Slave
node address 5
Slave Diagnosis/Statistics Tab Page
The number of error frames for the input port (PortA) for node address 4 is 31, so you can see
that error frames were received on the input port for node address 4.
Therefore, you can assume that there is a problem between the output port (PortB) for node ad-
dress 3 and the input port for node address 4.
This corresponds to location (A) (B) or (C) in the network configuration diagram.
Concretely, you can assume the following possible error locations.
• The device at node address 3
• The cable between the output port at node address 3 and the input port at node address 4 or
the connectors at those ports
• The device at node address 4
9 Troubleshooting
9-7
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
9-2
T
roubleshooting
9
9-2-4
Diagnostic and Statistical Information
Содержание NJ101-10 Series
Страница 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 68: ...2 Part Names and Slave Settings 2 18 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Страница 279: ......