5-8
Using the Sysmac Studio to Obtain
Serial Numbers from the Actual Net-
work Configuration
If the
Serial Number Check Method
in the EtherCAT master settings is set to
Setting = Actual
device
, you must download the network configuration information in which the slave serial numbers
are set to the CPU Unit.
Use the following procedure to get the serial numbers of the physical slaves and apply them as the
serial numbers of the slaves in the settings on the Sysmac Studio.
1
Start the Sysmac Studio and go online with the Controller.
2
Double-click
EtherCAT
under
Configurations and Setup
on the Multiview Explorer. Or, right-
click
EtherCAT
under
Configurations and Setup
and select
Edit
.
3
Right-click the EtherCAT master that is displayed in the EtherCAT Tab Page and select
Get
Slave Serial Numbers
.
The serial numbers of the physical slaves are saved as the serial numbers in the slave settings
on the Sysmac Studio.
5 Setting Up EtherCAT Communications with the Sysmac Studio
5-43
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
5-8 Using the Sysmac Studio to Obtain Serial Numbers from the Actual Network
Configuration
5
Содержание NJ101-10 Series
Страница 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 68: ...2 Part Names and Slave Settings 2 18 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Страница 279: ......