4
If there are slaves for which the node address is not set (i.e., for which the
present value
is 0)
or if there is more than one slave with the same node address (indicated by ), change the
set
values
of the slave addresses, and then click the
Write
Button.
(If the correct node addresses are set for all of the slaves, click the
Cancel
Button.)
Node addresses changed.
The node addresses are written to the actual slaves.
5
Cycle the power supply to the slave for which
Set value
of the node address is changed.
The set node address becomes valid.
6
Click the
Update With Latest Actual Network Configuration
Button.
The present values of each slave node address are read and
Present value
of node address-
es are updated. Check that
Present value
and
Set value
of the slave node address for which
Set value
was changed show the same values.
Version Information
Sysmac Studio version 1.22 or higher is required to use the
Update With Latest Actual
Network Configuration
Button.
When the Slave Node Address Writing Dialog Box Is Not Displayed
After you execute
Write Slave Node Address
and even several tens of seconds has passed, an
error message may be displayed, instead of the
Slave Node Address Writing
Dialog Box.
The following are causes that the error message is displayed.
• The communications cable is not wired correctly.
• More than the maximum number of slaves are connected.
Make suitable corrections according to the displayed message and then write the slave node ad-
dress again.
Refer to
5-6-3 When Compare and Merge with Actual Network Configuration Dialog Box Is Not
on page 5-32 for how to handle error messages.
2 Part Names and Slave Settings
2-11
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
2-2
Setting the Node Addresses of the Ether-
CA
T Slaves
2
2-2-2
Setting the Node Address from the Sysmac Studio
Содержание NJ101-10 Series
Страница 10: ...Manual Structure 8 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 68: ...2 Part Names and Slave Settings 2 18 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 80: ...3 EtherCAT Communications 3 12 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 236: ...9 Troubleshooting 9 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 274: ...Appendices A 38 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505...
Страница 275: ...I Index I 1 NJ NX series CPU Unit Built in EtherCAT Port User s Manual W505 I...
Страница 279: ......