Setting Control Specifications
Section 5-3
5-3
Setting Control Specifications
5-3-1
Starting and Stopping Control
■
Start Control (RUN) and Stop Control (STOP)
The following two methods can be used to start/stop control. For details, refer
to the corresponding pages.
1.
Starting/stopping control with an operation command: 6-4-11 Operation
Commands
2.
Starting/stopping control with an event input: 5-7-2 Event Inputs (TC2)
■
Operation After Power ON
The operation after power goes ON can be set to Continue, Stop, or Manual
mode operation. This setting also applies to operation after a software reset.
Note
This parameter can be set only when operation is stopped.
When this parameter has been changed, the new setting becomes effective
the next time a software reset is performed for the Unit or the next time power
is turned ON.
Variable type
Parameter name
Setting range
Default
F0/B0
Operation After Power ON
(Common)
0: Continue
1: Stop
2: Manual Mode
0
Conditions for use
No special conditions.
Operation
After Power ON
Operation
2-PID control
Continue
RUN/STOP
Retains the status that existed before power went OFF.
Auto/Manual
Retains the status that existed before power went OFF.
Manipulated
variable
• For Auto mode before power OFF:
MV depends on RUN/STOP status. When set to RUN,
operation starts from the initial value. When set to STOP,
operation starts from the MV at Stop parameter setting.
• For Manual mode before power OFF:
The manipulated variable from before power was inter-
rupted is maintained.
Stop
RUN/STOP
Stop
Auto/Manual
Retains the status that existed before power went OFF.
Manipulated
variable
• For Auto mode before power OFF:
Operation starts from the MV at Stop parameter setting.
• For Manual mode before power OFF:
The manipulated variable from before power was inter-
rupted is maintained.
Manual mode
RUN/STOP
Retains the status that existed before power went OFF.
Auto/Manual
Manual
Manipulated
variable
• For Auto mode before power OFF:
Operation starts from the MV at Stop parameter setting.
• For Manual mode before power OFF:
The manipulated variable from before power was inter-
rupted is maintained.
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......