63
Setting Input Specifications
Section 5-1
Simple Shift:
One-point Shift
The temperature measurements at all points in the sensor range are shifted.
For example, make the following settings if you want to increase the tempera-
ture by 1.2°C.
• Input Shift 1 = Input Shift 2 = 1.2
Note
It is not necessary to set the Input Value 1 for Input Correction or Input Value
2 for Input Correction parameters. Leave these parameters set to their default
settings.
When the measured value after the setting is 200°C, the process value will
become 201.2°C
Advanced Shift:
Two-point Shift
A linear compensation can be applied by setting the Input Value 1 for Input
Correction in Input Shift 1 and independently setting the Input Value 2 for
Input Correction in Input Shift 2. If different shift values are set for Input Shift 1
and Input Shift 2, the slope of the line may be different before and after apply-
ing the input shift.
Calculating Input
Shift Values
Measure the temperature at two points: the present value displayed by the
EJ1G and the location (control target) that needs to be displayed.
Preparations
1.
Set the input type to match the sensor being used.
2.
Prepare a thermometer capable of measuring the temperature of the con-
trol target as shown in the following diagram so that a 2-point shift can be
performed.
Input
Temperature
0
Input shift value
After
shifting
Before
shifting
After shifting
Before
shifting
Input Value 2
for Input Correction
Input
Display
0
Input Value 1
for Input Correction
Input Shift 1
Input Shift 2
(A) EJ1G Temperature Controller
(B) Thermometer
500
°
C
550
°
C
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......