Setting Alarm Specifications
Section 5-4
5-4-5
Alarm Latch
The alarm latch can be used to keep an alarm ON once it goes ON.
The latch can be released to turn OFF the alarm by executing an operation
command (Latch Cancel or Software Reset). Refer to 6-4-11 Operation Com-
mands for details on the operation commands.
Note
This parameter can be set only when operation is stopped.
5-4-6
Closed in Alarm or Open in Alarm
When Close in Alarm is set, the alarm output function's status will be output
as-is. When Open in Alarm is set, the alarm output function's status will be
reversed before being output.
The alarm output will be OFF (open) when the power is interrupted and for
about 3 seconds after the power is turned ON, regardless of the Close in
Alarm/Open in Alarm setting.
Note
This parameter can be set only when operation is stopped.
5-4-7
Alarm SP Selection
During SP ramping, this parameter specifies whether alarm operation is per-
formed on the ramping SP or the SP that will be reached after ramping.
Variable type
Parameter name
Setting range Default
E3/A3
Alarm 1 to 3 Latch
(Channel) 0: Disabled
1: Enabled
0
Conditions for use
The alarm type must not be set to 0.
Alarm Output Function
Alarm Output
Close in Alarm
ON
ON
OFF
OFF
Open in Alarm
ON
OFF
OFF
ON
Variable type
Parameter name
Setting range Default
E3/A3
Alarm 1 to 3 Open in Alarm
(Channel)
0: Closed
1: Open
0
Conditions for use
No special conditions.
Time
Temperature
Alarm output ON
Alarm output ON
Using the Ramping SP
Time
Temperature
Alarm output ON
Alarm output ON
Using the SP
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......