199
Status Lists
Appendix
Configuration Error A Status
Configuration Error B Status
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Undefined Expand
Units.
No error
Error
A Unit that is not recoginized is connected.
Bit 1
No Basic Unit
No error
Error
No Basic Units are registered and no TC4/TC2
Units are connected.
Bit 2
Too Many Basic Units
No error
Error
More than 16 TC4/TC2 Units are connected.
Bit 3
Not used.
Bit 4
Basic Unit Connection
Fault
No error
Error
The configuration has been registered, but the reg-
istered TC4/TC2 Units cannot recoginized.
Bit 5
Basic Unit Startup Error
No error
Error
A configuration error has occurred for the TC4/TC2
Units.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Illegal Unit Arrangement No error
Error
A Unit is connected to the left of the HFU.
Bit 9
Not used.
Bit 10
Not used.
Bit 11
Not used.
Bit 12
Illegal Restart Error
No error
Error
Only the HFU was reset during operation.
Bit 13
Invalid Registration
Error
No error
Error
The configuration registered without any TC4/TC2
Units.
Bit 14
Control Group Setting
Error
No error
Error
There is an error in the group settings.
Bit 15
Not used.
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Basic Unit 1 Error
No error
Error
An error occurred in a TC2 or TC4 Unit after the
configuration was registered.
Bit 1
Basic Unit 2 Error
No error
Error
Bit 2
Basic Unit 3 Error
No error
Error
Bit 3
Basic Unit 4 Error
No error
Error
Bit 4
Basic Unit 5 Error
No error
Error
Bit 5
Basic Unit 6 Error
No error
Error
Bit 6
Basic Unit 7 Error
No error
Error
Bit 7
Basic Unit 8 Error
No error
Error
Bit 8
Basic Unit 9 Error
No error
Error
Bit 9
Basic Unit 10 Error
No error
Error
Bit 10
Basic Unit 11 Error
No error
Error
Bit 11
Basic Unit 12 Error
No error
Error
Bit 12
Basic Unit 13 Error
No error
Error
Bit 13
Basic Unit 14 Error
No error
Error
Bit 14
Basic Unit 15 Error
No error
Error
Bit 15
Basic Unit 16 Error
No error
Error
C4/84 0002
C4/84 0003
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......