37
Setup Procedure
Section 3-1
The following table shows the group settings for this example.
The HFU handles all of the operations for gradient temperature control and
2-PID control. The maximum number of enabled channels that can be con-
trolled is selected at the HFU from 4, 8, 16, or 32 channels, and that num-
ber of channels is allocated for the number of groups used.
In this example, the maximum number of enabled channels is three, so the
HFU allocates groups in units of four channels each. The HFU recognizes
the following channels for the Basic Unit.
Variable
type
Address
Parameter
Setting value
F1 (B1)
0000
Number of enabled groups
4
0100
Group 1
Initial Communica-
tions Unit No.
1
0101
Initial Channel
0
0102
Number of Enabled
Channels
3
0103
Control Type
0: Gradient tem-
perature control
0200
Group 2
Initial Communica-
tions Unit No.
2
0201
Initial channel
1
0202
Number of Enabled
Channels
3
0203
Control type
0: Gradient tem-
perature control
0300
Group 3
Initial Communica-
tions Unit No.
4
0301
Initial Channel
0
0302
Number of Enabled
Channels
3
0303
Control Type
0: Gradient tem-
perature control
0400
Group 4
Initial Communica-
tions Unit No.
5
0401
Initial Channel
1
0402
Number of Enabled
Channels
3
0403
Control Type
1: 2-PID control
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......