Determining the Error from the Current Situation for Temperature Control Errors
Section 7-6
Overshooting or Undershooting
Hunting
The troubleshooting items for connection and setting problems are the same as for overshooting and under-
shooting, above.
Possible cause
Countermeasure
Connection Measured temperature is wrong.
• Perform the action outlined in 7.5.
A general-purpose thermometer with slow thermal response
has been connected to a control system with fast thermal
response.
• Change to a sheathed thermometer.
Setting
The proportional band value is too low.
• Increase the proportional band within a range with an
acceptable response delay.
• Execute gradient tuning (GT) or autotuning (AT).
The integral time is too short.
• Increase the integral time within a range with an acceptable
response delay.
• Execute gradient tuning (GT) or autotuning (AT).
The derivative time is too short.
• Increase the derivative time within a range that does not
adversely affect the stability of stabilization band.
• Execute gradient tuning (GT) or autotuning (AT).
ON/OFF control is operating.
• Execute P control or PID control.
The control cycle is too long for the control system with its
fast thermal response.
• Shorten the control cycle.
The overlap band in the heating and cooling control is set to
a dead band by mistake.
• Set to an overlap band.
Possible cause
Countermeasure
Procedure The heater's heating capacity is too large for the heating
capacity of the control target.
• Use a heater with a heating capacity suitable for the control
target.
There is periodic disturbance, which changes the heating
capacity of the control target.
• Change to an environment with as little periodic distur-
bance.
Executing autotuning (AT).
• Hunting will not occur once autotuning has been completed.
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......