Determining the Error from the Current Situation for Output Errors
Section 7-7
7-7
Determining the Error from the Current Situation for
Output Errors
No Control Outputs. No Alarm Outputs.
Possible cause
Countermeasure
Connection Measured temperature is wrong.
• Perform the action outlined in 7.5.
The load polarity or connected terminals are wrong.
• Rewire correctly.
A load exceeding the output rating is connected.
• Reduce the load to within the rating.
• Get the Unit repaired if it is malfunctioning.
No power supply for the load is connected to the transistor
outputs.
• Use a power supply suitable for the output rating and load.
The polarity of the load power supply for transistor outputs is
incorrect.
• Rewire correctly.
Setting
Set the Operation After Power ON parameter to Stop.
• Execute a RUN (start operation) operation command after
the power is turned ON.
• Set the Operation After Power ON parameter to Continue.
Control does not start.
• Execute a RUN (start operation) operation command.
The specified channel is incorrect.
• Set the correct channel number.
The control output assignments are incorrect.
• Set the correct control output assignments.
The set point is incorrect.
• Set the correct set point.
The specified bank is incorrect.
• Set the correct bank.
A bank specification for all channels has been assigned to
an event input, and an unintended bank has been selected.
• Assign the bank of the channel for which the bank is to be
changed to an event input.
Alarm mode is set to 0 (no alarm).
• Set the correct alarm mode.
Alarm mode is set to an alarm with a standby sequence.
• Set to an alarm without a standby sequence.
The deviation alarm and absolute-value alarm settings for
alarm mode are incorrect.
• Set the correct alarm mode.
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......