Setting Input Specifications
Section 4-1
This parameter can be set only when operation is stopped.
Always set the Scaling Upper Limit > Scaling Lower Limit.
If the Scaling Lower Limit > Scaling Upper Limit, the larger value will function
as the Scaling Upper Limit.
■
Setting Example
In this example, scaling is set to display 0 to 5 V as 10.0% to 95.0%.
Scaling Upper Limit = 950
Scaling Lower Limit = 100
Decimal Point Position = 1
4-1-4
Input Filter
Sets the time constant of the digital input filter.
The following diagram shows the response of the digital filter to a step-wise
input of amplitude A.
Variable type
Parameter name
Setting range
Default
E0/A0
(See note.)
Scaling Upper Limit
(Channel)
−
1999 to 9999
1000
Scaling Lower Limit
(Channel)
−
1999 to 9999
0
Decimal Point Position (Channel) 0: ****
1: ***.*
2: **.**
3: *.***
1
Conditions for use
The input type must be set to analog input.
Variable type
Parameter name
Setting range
Default
D5/95
Input Digital Filter
(Channel) 0.0 to 999.9 Second
0.0
Conditions for use No special conditions
Time
A
(Time
constant)
0.63 A
PV before passing through filter
PV after passing through filter
Input digital filter
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......