205
Status Lists
Appendix
Channel Alarm Status
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Alarm 1
OFF
ON
An alarm 1 error has occurred.
Bit 1
Alarm 2
OFF
ON
An alarm 2 error has occurred.
Bit 2
Alarm 3
OFF
ON
An alarm 3 error has occurred.
Bit 3
Not used.
Bit 4
Not used.
Bit 5
Not used.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Not used.
Bit 9
Not used.
Bit 10
Basic Unit Error
No Error
Error
An input error has occurred or a communications
error or zero-cross error has occurred in the G3ZA
connected to the Basic Unit with the relevant chan-
nel.
Bit 11
Basic Unit Alarm
No Error
Error
A peak current overflow has occurred for the rele-
vant channel or an HB or HS alarm has occurred.
Bit 12
Set Point Limiter Out of
Range
No Error
Error
The set point is outside the set point limiter.
Bit 13
Set Value Limiter
Reverse Operation
No Error
Error
The upper and lower set point limits are reversed.
Bit 14
MV Limiter Reverse
Operation
No Error
Error
The upper and MV limits are reversed.
Bit 15
Not used.
C4/84 0102 (CH1)·0201 (CH2) to 4002 (CH64)
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......