182
Parameter List
Appendix
Note Valid after a Software Reset operation command or after power is turned ON. Refer to the G3ZA Multi-
channel Power Controller User’s Manual (Cat. No. Z200).
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
DA (9A)
Can be
changed
during
operation.
0100
G3ZA1 - CH1 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0101
G3ZA1 - CH2 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0102
G3ZA1 - CH3 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0103
G3ZA1 - CH4 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0104
G3ZA1 - CH5 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0105
G3ZA1 - CH6 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0106
G3ZA1 - CH7 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0107
G3ZA1 - CH8 Slope
H' 00000000 to H' 00000FA0 (0.0 to 400.0)
100.0
%
NUM
●
---
0108
G3ZA1 - CH1 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
0109
G3ZA1 - CH2 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010A
G3ZA1 - CH3 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010B
G3ZA1 - CH4 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010C
G3ZA1 - CH5 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010D
G3ZA1 - CH6 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010E
G3ZA1 - CH7 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
010F
G3ZA1 - CH8 Offset
H' FFFFF060 to H' 00000FA0 (
−
400.0 to 400.0)
0.0
%
NUM
●
---
0110
G3ZA1 - CH1 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
1
---
NUM
●
---
0111
G3ZA1 - CH2 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
2
---
NUM
●
---
0112
G3ZA1 - CH3 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
3
---
NUM
●
---
0113
G3ZA1 - CH4 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
4
---
NUM
●
---
0114
G3ZA1 - CH5 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
5
---
NUM
●
---
0115
G3ZA1 - CH6 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
6
---
NUM
●
---
0116
G3ZA1 - CH7 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
7
---
NUM
●
---
0117
G3ZA1 - CH8 Source Channel
H' 00000001 to H' 00000008 (1 to 8)
8
---
NUM
●
---
0118
G3ZA1 - CH1 Heater Burnout Detection Value
H' 00000000 to H' 00000032 (0 to 50)
0
A
NUM
●
---
0119
G3ZA1 - CH2 Heater Burnout Detection Value
H' 00000000 to H' 00000032 (0 to 50)
0
A
NUM
●
---
011A
G3ZA1 - CH3 Heater Burnout Detection Value
H' 00000000 to H' 00000032 (0 to 50)
0
A
NUM
●
---
011B
G3ZA1 - CH4 Heater Burnout Detection Value
H' 00000000 to H' 00000032 (0 to 50)
0
A
NUM
●
---
011C
G3ZA1 - CH1 SSR Short-circuit Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
011D
G3ZA1 - CH2 SSR Short-circuit Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
011E
G3ZA1 - CH3 SSR Short-circuit Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
011F
G3ZA1 - CH4 SSR Short-circuit Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
0120
G3ZA1 - CH1 Heater Overcurrent Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
0121
G3ZA1 - CH2 Heater Overcurrent Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
0122
G3ZA1 - CH3 Heater Overcurrent Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
0123
G3ZA1 - CH4 Heater Overcurrent Detection
Value
H' 00000000 to H' 00000032 (0 to 50)
50
A
NUM
●
---
0124
G3ZA1 - Offset Control
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
1
---
NUM
●
---
0180
G3ZA1 - Send Standby Time (See note.)
H' 00000000 to H' 00000063 (0 to 99)
20
ms
NUM
●
---
0181
G3ZA1 - Communications Timeout Time (See
note.)
H' 00000000 to H' 0000003C (0 to 60)
(Function stops when set to 0.)
0
min
NUM
●
---
0182
G3ZA1 - Setting Operation for Errors
H' 00000000: Continue with error clear (0)
H' 00000001: Continue without error clear (1)
H' 00000002: Stop (2)
0
---
NUM
●
---
0183
G3ZA1 - Offset Value
H' 00000000 to H' 000003E8 (0.0 to 100.0)
20.0
%
NUM
●
---
0184
G3ZA1 - Hysteresis
H' 00000001 to H' 0000000A (1 to 10)
1
A
NUM
●
---
Not used.
0200
G3ZA2 - CH1 Slope
The rest are the same as the G3ZA1.
··
·
··
·
0300
G3ZA3 - CH1 Slope
···
···
0400
G3ZA4 - CH1 Slope
···
···
0500
G3ZA5 - CH1 Slope
···
···
0600
G3ZA6 - CH1 Slope
···
···
0700
G3ZA7 - CH1 Slope
···
···
0800
G3ZA8 - CH1 Slope
··
·
··
·
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......