Using Tool Ports
Tool ports are used to make EJ1G settings using the EST2-2C-MV3 CX-
Thermo Support Software.
The E58-CIFQ1 USB-Serial Conversion Cable is required to make the con-
nection.
2-3-1
Procedure
1,2,3...
1.
Turn ON the power supply to the EJ1G.
Note
Do not connect the E58-CIFQ1 while the power supply to the EJ1G
is OFF. If the Cable is connected when the power to the EJ1G is
OFF, power will be supplied from the computer and impose a load
on the internal circuits of the EJ1G.
2.
Connect the Cable.
Connect the computer's USB port with the port A connector on the EJ1G
using the Cable.
3.
Install the driver.
A driver must be installed to use the Cable.
• When the Cable is connected with the computer, the OS will detect a
new device.
Follow the installation wizard instructions and install the driver.
Note
For details on installation methods, refer to the user's manual for
the E58-CIFQ1 USB-Serial Conversion Cable.
4.
Make the communications port settings.
The USB-Serial Conversion Cable is used to communicate with the COM
port of the computer.
Set the communications port (COM port) number to be used for the CX-
Thermo software to the COM port assigned to the Cable.
E58-CIFQ1
Computer
Port A connector
EDU Front View
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......