186
Parameter List
Appendix
Note Not valid when an NT Link is being used.
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
F0 (B0)
Enabled
after
resetting.
Not used.
0001
Operation After Power ON
H' 00000000: Continue (0)
H' 00000001: Stop (1)
H' 00000002: Manual mode (2)
0
---
Common
---
●
0002
Operation During Error (Selection A)
H' 00000000: Notification only (Continue) (0)
H' 00000001: MV at PV error (1)
H' 00000002: Control Stop (2)
0
---
Common
---
●
Not used.
0004
Operation During Error (Selection C)
The rest are the same as Operation During Error (Selection A).
0005
Operation During Error (Selection D)
The rest are the same as Operation During Error (Selection A).
Not used.
0021
Port C Communications Baud Rate
Not used.
7
---
Common
---
●
H' 00000003: 9.6 (3)
H' 00000004: 19.2 (4)
H' 00000005: 38.4 (5)
H' 00000006: 57.6 (6)
H' 00000007: 115.2 (7)
(kbps)
0022
Port C Communications Data Length
H' 00000000: 7 (0)
H' 00000001: 8 (1)
(bit)
1
---
Common
---
●
0023
Port C Communications Parity
H' 00000000: None (0)
H' 00000001: Even (1)
H' 00000002: Odd (2)
1
---
Common
---
●
0024
Port C Communications Stop Bits
H' 00000000: 1 (0)
H' 00000001: 2 (1)
(bit)
0
---
Common
---
●
0025
Port C Send Wait Time
H' 00000001 to H' 00000063 (1 to 99)
5
ms
Common
---
●
0026
Port A Communications Send Wait Time
H' 00000001 to H' 00000063 (1 to 99)
1
ms
Common
●
●
Not used.
0029
Proportional Band x10 Compensation
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
Common
●
---
0030
Programless Communications Protocol
Not used.
2
---
Common
---
●
H' 00000002: NT Link (1:N) (2)
Not used.
H' 00000005: MC protocol (format 5) (5)
0031
Programless Communications Upload Data
Area
NT Link (1:N)
H' 00000000: DM (0)
H' 00000001: EM0 (1)
H' 00000002: EM1 (2)
H' 00000003: EM2 (3)
H' 00000004: EM3 (4)
H' 00000005: EM4 (5)
H' 00000006: EM5 (6)
H' 00000007: EM6 (7)
H' 00000008: EM7 (8)
H' 00000009: EM8 (9)
H' 0000000A: EM9 (10)
H' 0000000B: EMA (11)
H' 0000000C: EMB (12)
H' 0000000D: EMC (13)
0
---
Common
---
●
MC protocol (format 5)
H' 00000000: Data register (D) (0)
H' 00000001: Link register (W) (1)
H' 00000002: File register (R) (2)
0
0032
Programless Communications Download Data
Area
NT Link (1:N)
H' 00000000: DM (0)
H' 00000001: EM0 (1)
H' 00000002: EM1 (2)
H' 00000003: EM2 (3)
H' 00000004: EM3 (4)
H' 00000005: EM4 (5)
H' 00000006: EM5 (6)
H' 00000007: EM6 (7)
H' 00000008: EM7 (8)
H' 00000009: EM8 (9)
H' 0000000A: EM9 (10)
H' 0000000B: EMA (11)
H' 0000000C: EMB (12)
H' 0000000D: EMC (13)
0
---
Common
---
●
MC protocol (format 5)
H' 00000000: Data register (D) (0)
H' 00000001: Link register (W) (1)
H' 00000002: File register (R) (2)
0
0033
Programless Communications Upload Start
Address
H' 00000000 to H' 00007FFF (0 to 32767)
0
---
Common
---
●
0034
Programless Communications Download Start
Address
H' 00000000 to H' 00007FFF (0 to 32767)
500
---
Common
---
●
0035
Programless Communications Receive Wait
Time (See note.)
H' 0000000A to H' 00002710 (10 to 10000)
2000
ms
Common
---
●
0036
Programless Communications Node Address
(See note.)
H' 00000000 to H' 00000063 (0 to 99)
0
---
Common
---
●
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...