190
Status Lists
Appendix
Configuration Error A Status
Configuration Error B Status
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Undefined Expand Units No error
Error
A Unit that is not recognized is connected.
Bit 1
Not used.
Bit 2
Too Many Expand units
No error
Error
More than 9 G3ZA Units are connected.
Bit 3
Expand Unit Failure
No error
Error
There is an error in communications with the G3ZA.
Bit 4
Expand Unit Connec-
tion Fault
No error
Error
A communications response has not been received
from a G3ZA after it was registered in the configura-
tion.
Bit 5
Not used.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Not used.
Bit 9
Not used.
Bit 10
No HFU
No error
Error
There is no HFU.
Bit 11
Not used.
Bit 12
Not used.
Bit 13
Not used.
Bit 14
Not used.
Bit 15
Not used.
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Expand Unit 1 Error
No error
Error
There is an error in communications with the
G3ZA1.
Bit 1
Expand Unit 2 Error
No error
Error
There is an error in communications with the
G3ZA2.
Bit 2
Expand Unit 3 Error
No error
Error
There is an error in communications with the
G3ZA3.
Bit 3
Expand Unit 4 Error
No error
Error
There is an error in communications with the
G3ZA4.
Bit 4
Expand Unit 5 Error
No error
Error
There is an error in communications with the
G3ZA5.
Bit 5
Expand Unit 6 Error
No error
Error
There is an error in communications with the
G3ZA6.
Bit 6
Expand Unit 7 Error
No error
Error
There is an error in communications with the
G3ZA7.
Bit 7
Expand Unit 8 Error
No error
Error
There is an error in communications with the
G3ZA8.
Bit 8
Not used.
Bit 9
Not used.
Bit 10
Not used.
Bit 11
Not used.
Bit 12
Not used.
Bit 13
Not used.
Bit 14
Not used.
Bit 15
Not used.
C4/84 0002
C4/84 0003
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......