170
Specifications
Appendix
Specifications
Ratings
HB (Heater Burnout) Alarms, HS (Heater Short) Alarms
Note
(1) Heater burnouts and heater overcurrents are not detected if the control output (heating) ON time is
100 ms or less.
Detection is also sometimes not possible if a contactor is used for the control output.
(2) A heater short is not detected if the control output (heating) OFF time is 100 ms or less.
Detection is also sometimes not possible if a contactor is used for the control output.
TC4
TC2
HFU
EDU
Power supply voltage
24 VDC
Operating voltage range
85% to 110% of rated voltage
Power consumption (at maximum load)
5 W max.
4 W max.
2 W max.
---
Sensor inputs
Thermocouple
K, J, T, E, L, U, N, R, S, B, W, PLII
---
---
Platinum resistance
thermometer
Pt100, JPt100
---
---
Infrared Thermosensor
10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C
---
---
Analog
input
Current input 4 to 20 mA, 0 to 20 mA
---
Voltage input 1 to 5 V, 0 to 5 V, 0 to 10 V
---
Control outputs Voltage output
Output voltage: 12 VDC
Load current: 21 mA with short-circuit protection circuit
---
---
Transistor output
---
Max. operating voltage: 30 VDC,
max. load current: 100 mA,
residual voltage: 1.5 V max.,
leakage current: 0.4 mA max.
---
---
Auxiliary outputs (transistor outputs)
---
---
Max. operating voltage: 30 VDC,
max. load current: 50 mA,
residual voltage: 1.5 V max.,
leakage current: 0.4 mA max.
Event inputs
Leakage current
---
---
Approx. 4 mA
---
Contact input
---
---
ON: 1 k
Ω
max.,
OFF: 100 k
Ω
min.
---
Non-contact input
---
---
ON: Residual volt-
age: 1.5 V max.,
OFF: Leakage cur-
rent: 0.1 mA max.
---
Control method
---
---
2-PID or ON/OFF
control
---
Setting method
Via communications
Other functions
Depend on the model
Ambient temperature range
Operating:
−
10°C to 55°C, Stored:
−
25°C to 65°C (with no icing or condensation)
Ambient humidity range
Operating: 25% to 85%, Stored: 25% to 85%
Altitude
2,000 m max.
Inrush current (power supply)
Unit: 15 A or less
Installation environment
Overvoltage Category II, Pollution Class 2 (IEC 61010-1 compliant)
Maximum heater current
Single Phase 100 A AC
Input current indication accuracy
(±5% FS) ±1 digit max.
Heater burnout (HB) alarm setting range
0.1 to 99.9 A (in units of 0.1 A)
0.0 A:
Heater burnout (HB) alarm output turns OFF.
100.0 A:
Heater burnout (HB) alarm output turns ON.
Min. detection ON time: 100 ms (See note 1.)
Heater short (HS) alarm setting range
0.1 to 99.9 A (in units of 0.1 A)
0.0 A:
Heater short (HS) alarm output turns ON.
100.0 A:
Heater short alarm (HS) output turns OFF.
Min. detection OFF time: 100 ms (See note 2.)
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......