184
Parameter List
Appendix
Note The decimal point position is determined by the sensor selection. With analog inputs, the decimal point
position is determined by the Decimal Point Position B parameter setting. In this case, however, the 0
(****) decimal point position setting will be treated as a setting of 1 (***.*).
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
E3 (A3)
Can be
changed
while
stopped.
Not used.
0100
Alarm 1 Type - CH1
H' 00000000: Alarm function OFF (0)
H' 00000001: Upper and lower limit alarm (1)
H' 00000002: Upper limit alarm (2)
H' 00000003: Lower limit alarm (3)
H' 00000004: Upper and lower limit range alarm (4)
H' 00000005: Upper and lower limit alarm with standby
sequence (5)
H' 00000006: Upper limit alarm with standby sequence
(6)
H' 00000007: Lower limit alarm with standby sequence
(7)
H' 00000008: Absolute value upper limit alarm (8)
H' 00000009: Absolute value lower limit alarm (9)
H' 0000000A: Absolute value upper limit alarm with
standby sequence (10)
H' 0000000B: Absolute value lower limit alarm with
standby sequence (11)
2
---
CH
---
●
0101
Alarm 1 Latch - CH1
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
CH
---
●
0102
Alarm 1 Hysteresis - CH1
H' 00000001 to H' 0000270F (1 to 9999)
2
EU (See
note.)
CH
---
●
0103
Alarm 1 Open in Alarm - CH1
H' 00000000: Close in alarm (0)
H' 00000001: Open in alarm (1)
0
---
CH
---
●
0106
Alarm 1 SP Selection - CH1
H' 00000000: Ramp SP (0)
H' 00000001: Target SP (1)
0
---
CH
---
●
0107
Alarm 2 Type - CH1
The rest are the same as Alarm 1.
···
···
010E
Alarm 3 Type - CH1
··
·
··
·
Not used.
0200
Alarm 1 Type - CH2
The rest are the same as channel 1.
···
···
···
···
4000
Alarm 1 Type - CH64
TC4
---
···
···
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
E4 (A4)
Can be
changed
while
stopped.
Not used.
0101
Heater Burnout 1 Latch
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
IO
TC2
---
0102
Heater Burnout 1 Hysteresis
H' 00000001 to H' 000003E8 (0.1 to 100.0)
0.1
A
IO
TC2
---
0103
HS Alarm 1 Latch
H' 00000000: Disabled (0)
H' 00000001: Enabled (1)
0
---
IO
TC2
---
0104
HS Alarm 1 Hysteresis
H' 00000001 to H' 000003E8 (0.1 to 100.0)
0.1
A
IO
TC2
---
Not used.
0201
Heater Burnout 2 Latch
The rest are the same as from Heater Burnout 1 Latch to HS Alarm 1 Hysteresis.
···
···
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......