79
Setting Control Specifications
Section 5-3
• The disturbance response waveform can be adjusted with the Distur-
bance Gain and Disturbance Time Constant parameters.
Note
(1) This parameter can be set only when operation is stopped.
(2) The decimal point position is determined by the sensor selection. With
analog inputs, the decimal point position is determined by the Decimal
Point Position parameter setting. In this case, however, the 0 (****) deci-
mal point position setting will be treated as setting 1 (***.*).
■
Disturbance Gain
• Overshooting due to a disturbance can be suppressed more by increasing
the Disturbance Gain.
• Overshooting due to a disturbance can be increased by decreasing the
Disturbance Gain.
• If the Disturbance Gain is set to 0, the Disturbance Overshoot Adjustment
Function will not operate.
■
Disturbance Time Constant
The recovery time from the disturbance can be made longer by increasing the
Disturbance Time Constant. The Disturbance Time Constant is normally left
at its default setting of 1. Use this parameter for fine-tuning when adjusting the
Disturbance Gain alone is not sufficient.
Variable type
Parameter name
Setting range
Default
E5/A5 (See note 1.)
Disturbance Overshoot Adjustment
Function
(Common)
0: Disabled
1: Enabled
0
D5/95
Disturbance Gain
(Channel)
−
1.00 to 1.00
0.65
Disturbance Time Constant
(Channel)
0.01 to 99.99 s
1.00
Disturbance Rectification Band
(Channel)
0.0 to 999.9 EU
(See note 2.)
0.0
Disturbance Judgment Width
(Channel)
−
199.9 to 999.9 EU
(See note 2.)
0.0
Conditions for use
No special conditions.
0
SP
Temperature
Disturbance Gain =
−
1
Disturbance Gain =
−
0.5
Disturbance Gain = 0
Disturbance Gain = 0.5
Disturbance Gain = 1
Time
0
SP
Temperature
Disturbance Time Constant = 1
Time
Disturbance Time Constant = 2
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......