137
Detailed Description of Services
Section 6-4
6-4-6
Composite Read Registration
This service specifies the addresses to be read when using the composite
read registration from variable area service.
The registered data is saved in EEPROM.
■
Command
Service Request PDU
■
Response
Service Response PDU
1.
Variable Type and Read Address
Refer to Parameter List on page 175.
Composite reads/writes cannot be registered for the DA/9A variable types.
2.
Bit Position
The EJ1G does not support bit access. Fixed to 00.
3.
No. of Registered Data Items (Variable Type + Read A Bit Posi-
tion)
4.
Response Codes
MRC
2
2
0
1
4
SRC
2
2
0
0
2
4
2
0
0
1
1
Variable
type
Read address Bit
position
Variable
type
Read address Bit
position
Registered data length
No. of registered data items
For double-word (8-digit) variable type
20 max. (0014H)
For word (4-digit) variable type
Response code
Error name
Cause
1002
Command too short
The command is not long enough.
1101
Area type error
The corresponding variable type does not
exist.
1100
Parameter error
Bit position is not 00.Write data is out of
setting range.
2201
Operation error (2201) The command cannot be executed during
operation.
7011
Operation error (7011) The command cannot be executed due to
a device error.
7013
Operation error (7013) The command cannot be executed
because the operation command cannot
be received.
7014
Operation error (7014) The command cannot be executed during
backup.
7015
Operation error (7015) The command cannot be executed during
reset (including startup).
7041
Operation error (7041) The command cannot be executed in
manual operation mode.
7042
Operation error (7042) The command cannot be executed in tun-
ing mode.
0000
Normal completion
Processing was completed normally.
MRC
2
4
SRC
2
0
1
1
1
Response code
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......