181
Parameter List
Appendix
Note The decimal point position is determined by the sensor selection. With analog inputs, the decimal point
position is determined by the Decimal Point Position B parameter setting. In this case, however, the 0
(****) decimal point position setting will be treated as a setting of 1 (***.*).
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
D5 (95)
Can be
changed
during
operation.
0100
Input Digital Filter - CH1
H' 00000000 to H' 0000270F (0.0 to 999.9)
0.0
Seconds
CH
●
---
0101
Input Value 1 for Input Correction - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
EU
CH
---
●
0102
Input Shift 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
EU (See
note.)
CH
---
●
0103
Input Value 2 for Input Correction - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
1000
EU
CH
---
●
0104
Input Shift 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
EU (See
note.)
CH
---
●
0105
MV at PV Error - CH1
Standard Control:
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
0
%
CH
---
●
Heating and Cooling Control:
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
0106
MV at Stop - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
0
%
CH
---
●
Not used.
0109
MV Upper Limit - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
H' 00000000 to H' 0000041A (
−
0.0 to 105.0)
105.0
%
CH
---
●
010A
MV Lower Limit - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
H' FFFFFBE6 to H' 00000000 (
−
105.0 to 0.0)
−
105.0 %
CH
---
●
010D
Alpha - CH1
H' 00000000 to H' 00000064 (0.00 to 1.00)
0.65
---
CH
---
●
010E
Manual MV - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
H' FFFFFBE6 to H' 0000041A (
−
105.0 to 105.0)
0
%
CH
---
●
010F
SP Upper Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
9999
EU
CH
---
●
0110
SP Lower Limit - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
−
1999
EU
CH
---
●
0111
Disturbance Gain - CH1
H' FFFFFF9C to H' 00000064 (
−
1.00 to 1.00)
0.65
---
CH
---
●
0112
Disturbance Time Constant - CH1
H' 00000001 to H' 0000270F (0.01 to 99.99)
1.00
Seconds
CH
---
●
0113
Disturbance Rectification Band - CH1
H' 00000000 to H' 0000270F (0 to 9999)
0
EU (See
note.)
CH
---
●
0114
Disturbance Judgment Width - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
EU (See
note.)
CH
---
●
0115
Control Balance Coefficient - CH1
H' 00000000 to H' 00000063 (0.00 to 99.99)
0.80
---
CH
---
●
Not used.
0200
Input Digital Filter - CH2
The rest are the same as channel 1.
···
···
···
···
0400
Input Digital Filter - CH64
···
···
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
D6 (96)
Can be
changed
during
operation.
0100
Heater Burnout 1 Detection - CH1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
0.0
A
IO
---
●
0101
HS Alarm - CH1
H' 00000000 to H' 000003E8 (0.0 to 100.0)
100.0
A
IO
---
●
Not used.
0200
Heater Burnout Detection - CH2
The rest are the same as channel 1.
···
···
···
···
4000
Heater Burnout Detection - CH64
··
·
··
·
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
D7 (97)
Can be
changed
during
operation.
0004
Programless Upload Settings 4
0900
---
NUM
---
●
0005
Programless Upload Settings 5
0B00
---
NUM
---
●
0006
Programless Upload Settings 6
00FF
---
NUM
---
●
···
···
···
···
···
···
···
···
012F
Programless Upload Settings 303
00FF
---
NUM
---
●
Variable
type
Category
Add-
ress
Parameter name
Setting (monitor) range
Defau-
lt
Unit
Attribut-
es
Target Unit
TC4/
TC2
HFU
D8 (98)
Can be
changed
during
operation.
0004
Programless Download Settings 4
0940
---
NUM
---
●
0005
Programless Download Settings 5
0B40
---
NUM
---
●
0006
Programless Download Settings 6
00FF
---
NUM
---
●
···
···
···
···
···
···
···
···
012F
Programless Download Settings 303
00FF
---
NUM
---
●
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......