68
Setting Control Specifications
Section 5-3
5-3-2
Selecting the Control Method
Gradient temperature control or 2-PID control can be selected as the control
method.
Note
The control method can be set only while operation is stopped.
If the control method is changed, execute a software reset or cycle the power
to enable the setting.
Gradient Temperature
Control
Gradient temperature control is set using the Proportional Band (P), Integral
Time (I), Derivative Time (D), and Control Balance Coefficient parameters.
■
PID Settings
When using gradient temperature control, use gradient tuning (GT) to set the
PID constants.
Gradient tuning will automatically set the optimum PID constants (i.e., the pro-
portional band, integral time, and derivative time).
Note
Refer to 5-3-6 Tuning for information on gradient tuning (GT).
Note
(1) Refer to 5-7-1 Bank Function for information on bank specifications.
(2) The decimal point position is determined by the setting for the Decimal
Point Position B parameter. If, however, the Decimal Point Position B pa-
rameter is set to 0 (****), it will be treated as setting 1 (***.*).
If the temperature fluctuates even after GT has been executed, adjust using
the same PID constants for all channels in the group. The method for adjust-
ing PID is the same as for adjusting PID for 2-PID control. If the performance
is still unsatisfactory, use the rules outlined in the following table to adjust the
PID for the appropriate channel.
Variable type
Parameter name
Setting range
Default
F1/B1
Control Type
(Group) 0: Gradient tem-
perature control
1: 2-PID control
0
Conditions for use
No special conditions.
Variable type
Parameter name
Setting range
Default
D0/90
Proportional Band
(Bank) 0.1 to 999.9 EU
(See note 2.)
8.0
Integral Time
(Bank) 0 to 3999 Seconds
233
Derivative Time
(Bank) 0.0 to 999.9 Seconds
40.0
Conditions for use
No special conditions.
If the temperature is fluctuating for all
channels:
Adjust the PID for the initial channel.
If the temperature for the initial channel
is fluctuating:
Adjust the PID for the initial channel and
channel 1.
If the temperature is fluctuating for the
last channel:
Adjust the PID for the last channel.
If the temperature is fluctuating for a
channel other than those outlined above:
Adjust the PID for that channel and the
next channel.
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......