204
Status Lists
Appendix
Device B Status
Channel Status
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Save RAM 1
No Error
Error
Power was turned OFF while saving RAM1 and not
all data was registered.
Bit 1
Save RAM 2
OFF
ON
Power was turned OFF while saving RAM2 and not
all data was registered.
Bit 2
Save Control Parame-
ters
No Error
Error
Power was turned OFF during parameter registra-
tion after autotuning or GT was completed, and not
all data was registered.
Bit 3
Registration of unit con-
figuration/Registration of
multiple reads
OFF
ON
Power was turned OFF during Unit configuration
registration or composite read registration and not
all data was registered.
Bit 4
Not used.
Bit 5
Not used.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Write Mode
Backup
RAM write
Write mode can be confirmed.
Bit 9
EEPROM
RAM =
EEPROM
RAM
≠
EEPROM
Can confirm whether or not the setting is registered
in EEPROM.
Bit 10
Not used.
Bit 11
Not used.
Bit 12
Configuration Regis-
tered
Not regis-
tered
Registered
Configuration registration status can be confirmed.
Bit 13
Not used.
Bit 14
Not used.
Bit 15
Not used.
Bit position
Status
Bit description
Meaning
0
1
Bit 0
RUN/STOP
Run
Stop
Run/Stop can be confirmed.
Bit 1
Auto/Manual
Auto
Manual
Auto/Manual can be confirmed.
Bit 2
AT(GT) Execute/Cancel
AT(GT) is
stopped.
AT(GT) exe-
cution in
progress.
Can confirm AT(GT) Execute/Cancel.
Bit 3
Not used.
Bit 4
Control Type
Gradient
2-PID
Can confirm the control type.
Bit 5
Not used.
Bit 6
Not used.
Bit 7
Not used.
Bit 8
Input Error
No error
Error
An input error has occurred.
Bit 9
Not used.
Bit 10
Not used.
Bit 11
Not used.
Bit 12
GT Error
No error
Error
An error occurred while executing GT.
Bit 13
GTC Error
No error
Error
There is an error in internal parameters for GTC.
Bit 14
Not used.
Bit 15
Not used.
C4/84 0013
C4/84 0101 (CH1)·0201 (CH2) to 4001 (CH64)
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......