91
Detecting Current Errors
Section 5-5
Note
(1) In the above diagram, power is considered to be OFF (normal) if the leak-
age current is less than the HS alarm current during the OFF time. If the
SSR output is short-circuited, the measured current will increase beyond
the HS alarm value and an HS Alarm will be output.
(2) HS alarms are not detected if the control output (heating) OFF time is
100 ms or less. Detection is also sometimes not possible if a contactor is
used for the control output.
(3) The HS Alarm can be forced ON or OFF, regardless of the actual leakage
current value, by setting the HS Alarm parameter to 0.0 or 100.0. Use the
0.0 and 100.0 settings to check operation.
(4) This parameter can be set only when operation is stopped.
The hysteresis setting prevents chattering at the detection point.
When this parameter has been changed, the new setting becomes effec-
tive the next time a software reset is performed for the Unit or the next
time power is turned ON.
• Control will be continued even when there is an HS Alarm.
• The rated current value may sometimes differ slightly from the actual cur-
rent flowing to the heater. Check the current value in an actual operating
state in the Leakage Current Value Monitor parameter.
• If there is little difference between the current in normal and abnormal
states, detection may become unstable. To stabilize detection, set a cur-
rent value difference of at least 1.0 A for heaters of less than 10.0 A, and
at least 2.5 A for heaters of 10.0 A or more. If the heater current is too low,
loop the load line several times through a CT, as shown in the diagram
below. Looping it through once will double the detection current.
Control output (heating)
ON
OFF
ON time
OFF time
(See note 2.)
Variable type
Parameter name
Setting/monitoring
range
Default
D6/96
(See note 3.)
HS Alarm 1 or 2
(Channel) 0.0: HS Alarm ON
0.1 to 99.9 A
100.0: HS Alarm OFF
100.0
E4/A4
(See note 4.)
HS Alarm 1 or 2 Hysteresis
(I/O)
0.1 to 100.0 A
0.1
C5/85
Leakage Current Value 1 or
2 Monitor
(Channel)
0.0 to 110.0 A
---
Conditions for use
There must be a CT input.
CT
Load line
Содержание EJ1G
Страница 1: ...USER S MANUAL Modular Temperature Controllers for Gradient Temperature Control EJ1G Cat No H143 E1 01 ...
Страница 3: ...iv ...
Страница 17: ...xviii ...
Страница 21: ...xxii ...
Страница 53: ...32 Unit Configuration Examples Section 2 4 ...
Страница 69: ...48 Changing SPs During Operation Section 3 3 ...
Страница 81: ...60 Other Functions Section 4 5 ...
Страница 145: ...124 Other HFU Functions Section 5 7 ...
Страница 167: ...146 Detailed Description of Services Section 6 4 ...
Страница 189: ...168 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 7 8 ...
Страница 229: ...208 Parameters That Can Be Allocated for Programless Communications Appendix ...
Страница 237: ......