NSC Sicherheitstechnik GmbH
62/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
By pressing the "Details" key F3 the addresses of the modules can be checked.
Example:
Internal Modules
01/63
>01 FRP with FBC
A B
02 Remote LCD Panel
A
03 Remote LCD Panel
A
04 FRP
A B
05 -
06 -
Cancel
Details
By letters "A" und "B" will be displayed, on which channel of the redundant RS485 bus each
device has been connected.
Addresses of the RS485 devices correctly set?
Ο
Ok
Ο
fault
Wiring of the RS485 devices correct?
Ο
Ok
Ο
fault
Addressable detectors/modules
During the initialisation permanently a counter will be displayed which is counting the total number of
all detectors and modules. After scanning the loop devices, a list of these devices will be displayed.
This list will be visible each time the number of recognised detectors/modules has changed after
scanning the loops. Therefore after first time initialisation process all new recognised
detectors/modules will be listed.
Example:
Detector configuration 0001/0265
Seg. |Add| Error | Zone |Detect
>01 o 1|001| new | 0000 | 000
01 o 1|002| new | 0000 | 000
01 o 1|003| new | 0000 | 000
01 o 1|004| new | 0000 | 000
01 o 1|005| new | 0000 | 000
continue all ok ok
In line 1 the number of all recognised detectors and modules will be displayed. In the table for each
device will be displayed:
- Segment, where the device is connected to
- Symbol for loop "o" or spur wiring "-"
- Number of loop/spur
- configured device address
- Error code ("new" in this example)
- programmed zone and detector number
By pressing the "ok" key each single detector can be stored in the FCP programming, by pressing "all
ok" all connected devices will be stored in the FCP flash memory simultaneously.