for loop sounders).
See technical device specification for details of
functionality of each device type.
Note :
Sounder output modules are generally operated like
sounders / strobes connected to the monitored power
outputs : If the push button
is pressed they are
silenced.
108
Settings Input 001
with monitoring : No
Switch : Yes
Push button : No
Activation delay : 000
Cancel No Yes save
Automatic Control: Settings of 8 internal
monitored inputs
The picture on the left side shows an example of input
1 (indicated in the first line of the LC module).
These inputs can be configured :
With monitoring (only wire break) or without
(default value)
whether a switch or a push button is
connected to the input
With or without activation delay. The delay
can be adjusted in steps by one from 1 – 250
seconds.
0 means no delay.
The functions are disabled by F2 ("No") and the
functions are enabled by F3 ("Yes").
After setting the parameters please press F4
("Enter") to save the configuration.
109
Zones
Seg. : 1
from address : 1
to address : 12
Zone : 32
from detector : 1
Cancel save
Configuring zones (loop)
Please type the loop number (”Seg.”) and the
detector address (from – to).
Segment = Section of addresses (loop) with a
maximum of 254 Hochiki detectors, modules /
base sounders and a maximum of 126 Apollo
detectors, modules. The segment are partitioned
on the loop card according this list :
Loop card 1 : Segment 1 and 2
Loop card 2 : Segment 3 and 4
Loop card 3 : Segment 5 and 6
Loop card 4 : Segment 7 and 8
Loop card 5 : Segment 9 and 10
Loop card 6 : Segment 11 and 12
Loop card 7 : Segment 13 and 14
Loop card 8 : Segment 15 and 16
Loop card 9 : Segment 17 and 18
Address = Detector address (physical address stored
in the detector).
Zone = logical group of detectors (software zone)
where the detectors should be in
from detector = means the starting number of the
detector in the new zone.
Please confirm every line by "OK” and after finishing
all lines press "save" (F4) to save the new
configuration.