Following status are possible:
•
0 = inactive
•
1 = active
•
x = reset
•
= open circuit
•
S = short circuit
•
U = undefined
The last but one line shows any additional fault
information if the detector/module is not in normal
condition (here: fault because detector is missing).
Leaving the menu by pressing F1 ("Cancel").
28.1
Hochiki ESP
0002/001 opt. det. ALG-E
Configured detector text
A-Value
████████
0,8%/m
Pre alarm
███████████████
2,7%/m
Alarm
█████████████████
3,4%/m
Cancel Calib. Details
Apollo
0002/001 opt. det. XP95
Configured detector text
A-Value
█████
025
Pre alarm
██████████
045
Alarm
████████████
055
Cancel Compens. Details
Example of detector data: Optical smoke
detector
The FCP displays the current values of the detector
as horizontal bar charts. The meanings of the bars
are :
•
Analogue value (measured in detector
chamber)
•
Pre alarm threshold
•
Alarm threshold
The percentage values on the right relates to the bar
charts.
The Pre alarm/alarm threshold depend on
a) the detector sensitivity which can be
adjusted
b) the mode if the detector is a multi sensor
Only for Hochiki ESP
The push button "Calib"ration (F3) can be used to
calibrate an optical smoke detector or a multi sensor
manually. This will be done by the panel usually
automatically once a day (see Settings -> System
settings -> Parameter 12). That means usually this is
not necessary to do manually except :
1. after replacing a detector and if the fault
message "Calibration fault" appears.
2. if after the daily automatic calibration the
fault message "Calibration fault" appears.
The manual calibration process needs about 20 sec.
If in the second case the fault message does not
disappear the detector has to be replaced.
The push button "Details" (F4) shows the result of
the last calibration of the detector
Jump to Picture
30
.
Only for Apollo
By pressing "Compens."ation (F3) an automatic
smoke detector (Optical, Multi) can be readjusted
manually. This should be done, if a polluted detector
will be changed by a new one. By compensating the
detector the drift value (Discovery) or the alarm
threshold (XP95, XPlorer) will be reset. Without
manual compensation the FCP will adjust these