NSC Sicherheitstechnik GmbH
25/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
0002/001 Ion det. ACA-E
008 110 138 246
| | | |
______
|
______ ______
|
_____
Zeropoint Firepoint
61 190
Cancel
Only for Apollo Discovery
0002/001 opt. det. DISCOV.
Date of manufact. : 09/11
Pollution : 16
Sensitivity : 3
Last revision : -
Det.LED flash at poll. : 0
Cancel
A pollution fault will be generated automatically
at the following smoke densities::
opt. det. ALG-E
+- 1,1 %/m
Multisen ALG-E
+- 1,1 %/m
Ion det. ACA-E
+- 0,17%/m
Only for Apollo Discovery
The Apollo "Discovery" series has the ability to store
data in the flash memory of the detector itself. These
data remains in memory even if the detector will be
removed from the base. The reading and transmitting
of the data will last about 1-2 seconds. Therefore you
have a short delay before first value will be displayed.
The following data is available:
- date of manufacture of the detector in format
MM/JJ
- pollution in the range 0-31.
•
16 = clean air value
•
<=3 and 31 = pollution fault
•
0 = fault with analogue value 4
- sensitivity 1-5 (s. Picture
111
)
- date of last revision in format MM/JJ. If no revision
alarm has been activated for this detector a "-".will
be displayed.
- detector LED at polling
•
1 = LED flashes, if detector is polled.
•
0 = LED off, if detector is polled
this function can be set by system-parameter 8