NSC Sicherheitstechnik GmbH
67/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
Common technical data
Maximum number of zones per loop
127
Maximum number of addressable devices per loop
-
Hochiki: 127 detectors/m 127
base sounders
-
Apollo: 126 addressable devices
Maximum number of zones per FCP
-
1024 programmable
-
192 LED indicator
Maximum number of addressable devices per BMZ
-
Hochiki: 2286 detectors/m 2286
base sounders
-
Apollo: 2268 addressable devices
Alarm activation equipment per FCP
1
Quiescent current of FCP without loop cards:
90 mA
Quiescent current loop card B01260-00/B01262-00 :
33 mA (without detectors)
Quiescent current loop card B01270-00/B01272-00 :
38 mA (without detectors)
Quiescent current of conventional card B01300-00 :
30 mA (without detectors)
Quiescent current of conventional card B01310-00 :
35 mA (without detectors)
Quiescent current of relay card:
4 mA
Operating temperature:
-5 to +40° C
Humidity :
Max. 95 % rel. Air humidity
Housing :
Steel sheet, RAL 7035
Safety class:
IP 40
Dimensions housing A1, A2 :
540 x 492 x 162 mm (W x H x D)
Weight FCP Solution F1-6 in housing A1, A2 :
14 kg
Dimensions housing B1, B2 :
540 x 540 x 245 mm (W x H x D)
Weight FCP Solution F1-18 in housing B1, B2 :
18,5 kg