NSC Sicherheitstechnik GmbH
57/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
4. Mounting instruction
1. First please remove the cover of the FCP. You will find the key on the backside of the panel
housing.
2. The FCP "Solution F1" has a wall mounting housing. The B1 and B2 housings provide a
drilling template for easier mounting. Use this template for drilling the holes.
3. Please use 8mm dowels for fixing the screws. Don’t put the batteries into the panel yet. Start
with the upper screws; hang the back plate of the housing on the screws and then you can
screw the lower holes.
4. The control panel can be opened by unscrewing the plastic screws only on the right side of the
control panel, giving free access to the terminals for connecting the wires.
5. Don’t connect the panel to Mains AC yet. Use the wiring diagrams for connecting loops,
conventional zones and sounders / strobes.
6. If you are connecting the shielding of the loop wires (the FCP "Solution F1" does NOT need
that in any case but it can be advantageous to do so) then you have to connect the wire on
both sides at the loop card.
7. Please connect peripheral components like LCD repeater panels, remote control panels etc.
8. Now you have to connect the Mains AC cable. Make sure that the Mains AC fuse on the
power supply is plugged in.
9. Switch on Mains AC voltage.
10. If the internal buzzer sounds, please switch of by using push button
.
11. Put the batteries on the bottom of the panel housing and fix them by using the cable fixer.
Connect the batteries to the power supply by using the supplied cables (see wiring diagram).
12. Please follow the commissioning instruction.