NSC Sicherheitstechnik GmbH
56/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
Codes for inputs
Page 1
Code
1. Alarm 5. Switch on/off
2. Pre alarm 6. Revision
3. Main alarm 7. Change sensit.
4. Fault 8. Activation
Cancel Enter
Page 2
Code
1. Active 5. Installer
2. Inact.
3. Information
4. End user
Cancel Enter
Codes for special keys
Code
1. Switch on/off
2. Change sensit.
3. Activation
Cancel Enter
For codes "Alarm", "Pre alarm", "Main alarm",
"Fault" and "Switch off" additionally zone and
detector number can be put in.
To use it, a not existing address (virtual detector) has
to be programmed to that zone/detector number.
(s.
Alarm configuration - Zones ->Menu 109)
. This
also can be a detector on a not existing loop card.
Then activation of an input simulates message from a
detector and all programmable features of that
detector (i.e. customer text) or that zone (i.e. alarm
configuration) can be used.
By code "Revision" you can enter the one-man-
revision mode by activation of an input.
By code "Activation" directly outputs, relays, power
outputs or loop modules can be activated.
Code "Active" allows activating any system output by
an input signal, i.e. a push button. The same output
could be switched inactive by a different input
choosing the code "Inactive".
Code "Information" means, that only an activation
message will be generated but no alarm and no fault
message.
Code "End user" gives you the opportunity to enter
the second control level without typing in the end user
password, i.e. by connecting a key switch to an input
configured to "End user" code.
Code "Installer" is the same for installer password.