NSC Sicherheitstechnik GmbH
38/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
The shielding will be controlled under the following
conditions:
-
During detector scanning
-
ca. 15 seconds after FCP reset
-
every 24h during detector calibration
"Reset first alarm" has the effect, that in case of cross
zoning or cross detection the first alarm will be reset
automatically after the configured period if during this
time no further alarm rises.
The time "Calibration fault" determines a time, when a
fault message caused by a calibration error during
automatic 24h calibration will be displayed.
"Call acceptance after restart" has to be set to "1" if a
build in telephone modem shall be automatically
accept incoming calls after power up the system.
Parameter "printer" controls the line feed of a
connected printer.
05
Fault reset
0
Automatically
1
by "
"
06
Fault remind
0-30
Minutes or
0=no remind
07
Summer time
switching
0
Automatically
1
Off
08
Detector LED
flash at polling
0
Off
1
On
09
LED Intensity
(LEDs of FCP)
0-15
0= dark
7= standard
15= bright
10
Sounder output
Activation
0
In case of
main alarm
1
At any alarm
11
Power Supply
0
NSC PSU
1
external:
1 channel
2
external:
2 channel
3
SLAT PSU
4
New NSC
PSU
12
Calibration time
0-24
Corresponds
to time
13
Earth fault
detection
0
On
1
Off
14
Not used
15
Pre alarm
(for all detectors)
0
Off
1
On
16
Reset detector
test
0
Automatic
1
Manual
17
RS485 channels
1,2
Corresponds
to the numbers
of channels
18
Shielding
control
0-1
0 = off
1 = on
19
Buzzer at
information
0-1
0 = off
1 = on
20
Reset first
alarm
0,
5-99
Minutes
21
Calibration fault
0-23
time (hour)
22
Call accept.
after restart
0-1
0 = 0ff
1 = on
23
KDB activation
0-1
0 = main alarm
and feedback
1 = feedback
only
24
Printer
0-1
0 = CR (NSC
built in printer)
1 = CRLF
(ext. printer)