scanned. The number of found RS-485
devices will be displayed in the last but one
display line
Jump to Picture
79
7. Opens input screen "Modem"
Jump to
Menu
80
8. Opens input screen for network settings
Jump to Menu
81
9. Facilitates a software update of the main
board using the configuration software
Jump to Menu
82
For another settings menu please press F3 ("more")
to enter sub menu "Settings 3"
Jump to Menu
38
38
Settings 3
1. Power outouts
5. Arcnet
2. Loop parameters
6. Webserver
3. Options
4. Scan Modbus
Cancel Enter
Settings 3of FCP
1. Opens input screen to configure power
output settings
Jump to Menu
83
2. Opens input screen to configure loop
settings
Jump to Menu
84
3. Jumps into menu to unlock options
Menu
85
4. Scans Modbus devices connected to serial
interfaces of the FCP.
5. Menu to change the network communication
speed
Menu
87
6. Opens the menu to configure the webserver
module IP settings
Sprung in Menu
91
50
Detector test Status
Zone : 2 Normal
Detector : 3 Normal
Alarm unset (outputs inactive) !
Cancel On set
Example of detector test :
Detector not yet in alarm :
0002/002 opt. det.
ALG-E
Evt. individual detector text
A-Value
████████
0,0%/m
Pre alarm
███████████████
2,7%/m
Alarm
█████████████████
3,4%/m
Cancel Calib. Details
Detector in alarm :
0002/002 opt. det.
ALG-E
Evt. individual detector text
A-Value
██████████████████████
4,5%/m
Pre alarm
███████████████
2,7%/m
Alarm
█████████████████
3,4%/m
Cancel Calib. Details
Detector test (only for addressable
detectors)
First zone and detector number (within the zone) has
to be typed. Every line has to be confirmed by "OK”.
The push button F4 ("set / unset") can be used to
configure if the outputs of the FCP shall be activated
during the test alarm or not. The current selection is
displayed in the last but one line of the LC module
(here : "outputs inactive").
After that the test alarm can be activated by pressing
F2 ("On").
By using the "System Settings" (parameter 16) it is
possible to configure an auto-reset of the test alarm
condition or no auto-reset. In that case the test alarm
has to be reset by pressing "Reset"
.
The bar charts as in the example on the left side show
how the test alarm will arise (see A-value). If the
analogue value passes the alarm threshold the
detector goes into alarm condition.