NSC Sicherheitstechnik GmbH
9/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
one or two. It depends on the menu. Here we do not describe the function keys in details. Therefore
please have a look into section 2.
Please note that : usually there are the following standard functions for
"F1" = "cancel" or "back". Means to leave the current menu and jump into the menu
above, and
"F4" = "Enter". Means to select (or confirm) the function which is marked in the LC
module by a black background.
Description of the push buttons:
The control panel of the FCP "Solution F1" contains a brand new technology of push buttons. There
are no more mechanical push buttons or ordinary foil key pads but it is a pressure sensitive piezo
lacquer technology which is printed on the aluminum plate. These push buttons must not be
adjusted and this technology has not known any attrition or abrasion for many years and it is
very resistant to EMC interferences and detergents. An intelligent circuit detects any pressing of
the push buttons and confirms it by a beep.
The push buttons which are maybe not self-explanatory are these:
Push button :
Description :
By this push button the user leaves the normal operation and enters the main menu of
the FCP. See the detailed description in section 2.
This push button deactivates (switch off) the external sounder outputs in case of an
alarm. This is a temporary deactivation because if another alarm comes in the
sounders will be activated again.
−
This push button deactivates (switch off) the internal buzzer in case of an alarm or
fault message. This is a temporary deactivation because if another message
comes in the buzzer will be activated again.
−
In case of an alarm and if the alarm transmission is delayed, the delay time will be
started.
−
If there is no alarm and no fault this push button activates an LED test.
This push button resets the FCP.
In case of a key deposit alarm message you have to put in the installer code at first
and afterwards press this button.
Field programmable push buttons (S1 – S8). See detailed description in the installer
manual.
Use this push button in the menus to confirm your inputs line by line.
Use this push button in the menus to cancel your inputs.
Cursor control keypad.