The actual "status" of the relay (e.g. normal condition or
active) will be displayed behind the number.
After selection the relay / relays you have to switch
them by pressing F3 ("off") or F2 ("on").
09
Switch on/off FCP 001
from power output : 001 normal
to power output :
↓
+1
↑
-1 Selection -> +10 <- -10
>001 Power Output 001 Main processor
002 Power Output 002 Main processor
003 Power Output 003 Main processor
Cancel On Off Enter
Switching on/off: 3 internal power outputs
Here the 3 internal power outputs on the main
processor board of the FCP "Solution F1” can be
switched on/off.
To switch on/off the relays there are two possibilities
you can choose :
a) To type the power output no. directly by the
key pad and confirming with "OK". Please use
the line "from power output” and "to power
output” for this.
b) Select the power outputs by using the cursor
keys
↓
and
↑
(means 1 line up or 1 line down)
or the cursor keys
and
(means 10 lines
down or 10 lines up) and confirm the power
output numbers with "Enter" (F4) or "OK”.
The actual "status" of the power output (e.g. normal
condition, fault or active) will be displayed behind the
number.
After selection the power output / power outputs you
have to switch them by pressing F3 ("off") or F2 ("on").
10
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Transm.Dev
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: sounders / strobes
After selecting this function in the switch on/off main
menu you see at the bottom line of the LCD "off" (F3)
or "on" (F2).
By pressing F3 all sounders / strobes will be switched
off continuously.
Pay attention :
By the function (F3) all sounders and strobes will
be switched off continuously. If another alarm
comes in the sounders / strobes will not be
activated again until they are switched on again.
11
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: Alarm Transmission Device
(TD)
After selecting this function in the switch on/off main
menu you see at the bottom line of the LCD "off" (F3)
or "on" (F2).
By pressing F3 the Alarm transmission device will be
switched off continuously.
The current status of the TD will additionally indicated
by the yellow LED on the control panel.