Configure power outputs
Load resistance Tolerance
No.: ( old) Norm OC-Tol. Th.OC Th.SC
1 : (0983) 0983 + 120 = 1103 , 0727 Ohm
2 : (0977) 0977 + 120 = 1097 , 0724 Ohm
3 : (0964) 0964 + 120 = 1084 , 0717 Ohm
Cancel Calib. save
The thresholds depend on the load resistance of the connected device inclusive the line resistance.
This total resistance can be ascertained automatically for each power output individually by pressing
"calib." F3. The software then calculates the thresholds for open circuit and short circuit. The
resistance can also be measured with a multimeter and typed in directly using the keyboard.
Configuration of the fire control system
The configuration of the fire control system is very comprehensive and is mainly dependent of the
largeness of installation. The details have to be specified in the planning documents. The
following checklist describes the individual steps of the programming of the fire control panel:.
Programming
Menu topic
Zones
Alarm organisation
Ο
Ok
Detector configuration
- sensitivity
- mode of multi sensors
- time program
- pre alarm
- alarm delay
Alarm organisation
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Detector texts
by PC software
Ο
ok
Ο
not used
Programming
Menu topic
Zone parameters
- cross detection
- internal alarm zone
- fault zone
- manual call point (only for
conventional detectors or
modules)
Alarm organisation
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Cross zoning
Alarm organisation
Ο
ok
Ο
not used
Timer programs
- for delay
- for detector sensitivity
Alarm organisation
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Delay
Alarm organisation
Ο
ok
Ο
not used
Power outputs
- key deposit box
- sounders/flashlights
- transmission device
Automatic controlling
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Ο
ok
Ο
not used
Controlling of relays, outputs or
output modules
Automatic controlling
Ο
ok
Ο
not used
Loop sounders
Automatic controlling
Ο
ok
Ο
not used
Controlling by special keys
Configuration
Ο
ok
Ο
not used
System parameters
Configuration
Ο
ok
Ο
not used
Holidays
Configuration
Ο
ok
Ο
not used