elapsed, a fault message will be generated -> Menu
116
.
When you have finished data, time and weekday
please press F4 ("save") to save the new
configuration.
68
Holidays
Day : 25
Month : 12
↓
+1
↑
-1 Selection ->+10 <--10
01: Day 31 Month 12
>02: Day 00 Month 00
03: Day 00 Month 00
Cancel save
To configure Holidays
Please type the day of a holiday in the second line of
the LC display and the month in the third line. The
example on the left side shows Christmas holiday.
Please confirm every line by OK
The marker ">" indicates the number of holiday which
the user is configuring at the moment.
When you have finished day and month press F4
("save") to save the holiday. It will be transferred into
the list in the middle part of the LC display.
To cancel a holiday: Please put the marker ">" by
the cursor push buttons
↑
,
↓
on the holiday which shall
be erased and type "00" for day and month and save
it by F4.
69
System settings
FBC settings : 00
↓
+1
↑
-1 Selection ->+10 <--
10
>01: FBC settings (0-3) 00
02: Transm. Device settings(0-2) 00
03: FCP cover contact (0-2) 01
Cancel save
*) If the German Fire Brigade Control Panel is
connected to the "Solution F1" the following
outputs are occupied :
- Output OC 01 – 06 on main board
for NSC-FBC
- Output OC 01 – 07 on main board
for SeTec-FBC
- Input 01 – 05 on main board
(see wiring diagram)
System settings
Here the user can configure certain individual
software and hardware settings which are listed in the
table below.
The marker ">" indicates the kind of setting which the
user is configuring at the moment. It is displayed in
the 2nd line of the LC module.
Please select the setting by the cursor keys and type
the right value according the table below. The
possible values are listed in brackets.
If all settings are configured please press F4 ("save")
to save the new configuration.
The FCP supports the following settings :
Nr.
Parameter
Value Description
01
FBC
0
no FBC
(Fire Brigade
1 *)
NSC-FBC
Control Panel)
2 *)
SeTec-FBC
3
FBC
Switzerland
02
Transm. Device
0
Contin. signal
(TD)
1
puls signal
2
puls signal and
puls feed back
03
FCP cover
contact
0
Deactivated
1
Switch off TD
2
Switch on and
off TD
04
Mains fault
delay
only with FBC
Switzerland
(s. Parameter 1)
0-30
0-60
Minutes
Minutes