NSC Sicherheitstechnik GmbH
21/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
26.4
Internal Modules 01/63
>01 FRP with FBC
A B
02 Remote LCD Panel A
03 Remote LCD Panel A
04 FRP A B
05 -
06 -
Cancel Details
Display of FRP/LCD Panel
Different protocol can be set to each serial interface
of the FCP. (s. menu 113).
On all interfaces set to "FRP protocol" connected
devices will be scanned. The address range for these
devices is 1-63.
The device types will be shown as text.
Following devices are available:
FRP
FRP with FBC
FRP Munich
FRP with FBC Munich
Remote LCD Panel
PC Management system
LED mimic panel
Voice Evacuation System EVA8
If Voice Evacuation System is connected via serial
interface, it will automatically occupy address 63.
By characters "A" and "B" will be signalized, on which
channels a device has been connected.
For further information please press "Details" (F4)
jump to menu
29.1
26.5
Modbus device 01/63
>01 LISTEC SCU
02 -
03 -
04 -
05 -
06 -
Cancel Details
Display of Modbus devices
Different protocol can be set to each serial interface
of the FCP. (s. menu 113).
On all interfaces set to "Modbus protocol" connected
devices will be scanned. The address range for these
devices is 1-6.
The device types will be shown as text.
Following devices are available:
LISTEC SCU
The address of a SCU800 will be set by the
configuration software "Listterm". Addresses
from 1-8 are possible. Internally the FCP
handles each SCU800 like a loop card. Each
cable section represents one segment. A
maximum of 99 sensors is possible on each
section. The sensors can be configured to any
zone.
27
Network ID 002 FCP 002
ID-1 :002 Timeout 000
ID-2 :002 Timeout 000
Status 1 :00000000
Message :0951
from message :0951
Cancel Details
Details of network devices
The ID of first and second network card will be
displayed and additionally you can see if there are
still messages in the pipeline to be send to this
device. If the counter behind "Message" is different to
the counter behind "from message" not all messages
have been transferred to this device.
Timeout shows missing communication to another
network device in seconds. After 90 seconds a
network fault will be displayed.
The bit sequence "Status 1" contains the following
status information from right to left: