background image

 

 

 
NSC Sicherheitstechnik GmbH 

12/69 

14.08.2013 

Lange Wand 3 

B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 

33719 Bielefeld 

 

Version S040A13.08 

 

06 

Zones & detect.             FCP 001                                     

                          

Status   

from zone          : 5                                                          
programmed zone text 
To zone            :                                                                                                    
 
 
Cancel       On        Off      Detect.  

 

Switching on/off: zones and single detectors 

You can switch off single zones or several zones 
simultaneously. This is done by using the "from … to… 
" function. Please type the zone number and confirm by 
"OK”
"Status" means the current status of the zone (e.g. 
normal, alarm, fault). To switch off the zone you have to 
press "Off" (F3) or for switching on the zone you have to 
press "On" (F2)
 
If only one zone shall be switched the line "to zone" can 
be missed and F2/F3 (on/off) can be pressed 
immediately. 
If single detectors shall be switched you have to type 
"Detect.” (F4) after the zone has been confirmed (do 
not use F2/F3 (on/off) in this case) 

 Jump to Menu 

22

 

 

07 

Switch on/off                RCP 003 

 

from output       : 001         normal   
to output         :                      

+1  

-1    Selection   -> +10  <- -10  

>001 Output 001        Main processor        
 002 Output 002        Main processor        
 003 Output 003        Main processor     
Cancel      On        Off         Enter   

 

Switching on/off: OC-Outputs 

Here the 16 OC-outputs on the main processor board of 
the FCP "Solution F1” as well as the OC-outputs on the 
loop cards can be switched on/off.  
 
The outputs are located like this : 
Outputs 1 – 16 :     OC- Outputs on main board 
Outputs 17 – 24:    OC- Outputs on 1. loop card 
Outputs 25 – 32:    OC- Outputs on 2. loop card 
etc. 
 
To switch on/off the outputs there are two possibilities 
you can choose : 

a)  To type the output no. directly by the key pad 

and confirming with "OK". Please use the line 
"from output” and "to output” for this. 

b)  Select the outputs by using the cursor keys 

 

and 

 (means 1 line up or 1 line down) or the 

cursor keys 

  and 

  (means 10 lines down 

or 10 lines up) and confirm the output numbers 
with "Enter" (F4) or "Ok”. 

 
The actual "status" of the output (e.g. normal condition 
or active) will be displayed behind the number. 
 

After selecting the output / outputs you have to switch 
them by pressing F3 ("off") or F2 ("on")

 

08 

Switch on/off                FCP 001 

 

from relay       : 001         normal   
to relay         :                      

+1  

-1    Selection   -> +10  <- -10  

>001 Relay 001        Main processor        
 002 Relay 002        Main processor        
 003 Relay 003        Main processor       
Cancel      On        Off         Enter  

Switching on/off: 4 internal relays 

Here the 4 internal relays on the main processor board 
of the FCP "Solution F1” can be switched on/off. 
 
To switch on/off the relays there are two possibilities 
you can choose : 

a)  To type the relay no. directly by the key pad 

and confirming with "OK". Please use the line 
"from relay” and "to relay” for this. 

b)  Select the relays by using the cursor keys 

 

and 

 (means 1 line up or 1 line down) or the 

cursor keys 

  and 

  (means 10 lines down 

or 10 lines up) and confirm the relay numbers 
with "Enter" (F4) or "OK”. Then press "Enter" 
(F4) to confirm the switching.  

 

Содержание Solution F1

Страница 1: ...GmbH 1 69 14 08 2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814 doc 33719 Bielefeld Version S040A13 08 Fire Control Panel Solution F1 Operating and Installation Man...

Страница 2: ...NSC Sicherheitstechnik GmbH 2 69 14 08 2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814 doc 33719 Bielefeld Version S040A13 08...

Страница 3: ...of Power Supply Voltages 15 Example of Power Supply Status Information 16 Example of Power Outputs Voltages 16 Example of Input voltages 16 Example of displaying software version and Serial No 16 Swi...

Страница 4: ...igure Holidays 37 System settings 37 Scan detectors 39 Delete Configuration 39 Delete Texts 39 Delete Events 39 Configuring macro push buttons S1 S8 39 Changing the installer access code 40 Selecting...

Страница 5: ...58 Checking the wiring system 59 Measure end of line resistors of conventional zones without voltage 59 Measure cable resistance of loop wiring without voltage 59 Measurement of the end of line resist...

Страница 6: ...NSC Sicherheitstechnik GmbH 6 69 14 08 2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814 doc 33719 Bielefeld Version S040A13 08...

Страница 7: ...FCP is in operation green LED Day Mode Indicates that the FCP is in Day Mode That means the main alarm is delayed if a delay time is configured green LED Night Mode Indicates that the FCP is in Day Mo...

Страница 8: ...puts is switched off yellow LED System The FCP itself is in fault condition That means that maybe the main board micro controller does not work well and the correct function of the FCP is not guarante...

Страница 9: ...detects any pressing of the push buttons and confirms it by a beep The push buttons which are maybe not self explanatory are these Push button Description By this push button the user leaves the norma...

Страница 10: ...orked fire control panels After pressing F2 a list of all networked devices appears Menu 1 1 The push button Installer F3 is to use for the installer company only It leads to the menus for service and...

Страница 11: ...04 End user old access code 0000 new access code 3528 new access code 3528 Cancel Changing the end user access code First you have to type the old access code then you have to type two times the new a...

Страница 12: ...cated like this Outputs 1 16 OC Outputs on main board Outputs 17 24 OC Outputs on 1 loop card Outputs 25 32 OC Outputs on 2 loop card etc To switch on off the outputs there are two possibilities you c...

Страница 13: ...power output numbers with Enter F4 or OK The actual status of the power output e g normal condition fault or active will be displayed behind the number After selection the power output power outputs y...

Страница 14: ...is function disables in case of an alarm all outputs which have been configured with yes in the menu Automat Controlling Selection 1 to 4 Settings Operate like Fire Output These could be 3 internal po...

Страница 15: ...lect with the cursor keys the module which should be investigated more detailed and press Details F4 Jump to Menu 26 17 ID Type Zone offset Mode 001 FCP 001 01000 Day 002 FCP 002 02000 Night 003 RCP 0...

Страница 16: ...C F1 F4 fused 24VDC output 1 4 NT high voltage power regulator NT mains fault low voltage power regulator 19 Power outputs No Volt Th SC R Act Th OC Cal 1 1 89V 0735 0994 1117 0997 Ohm 2 1 89V 0735 0...

Страница 17: ...s which can be displayed in the LC module If a message is marked with x this message will be displayed If it is marked with this message will not be displayed You can switch from x to by push button F...

Страница 18: ...P HCP E Manual Call Point Sounder YBO BS Sounder YBO BSB Sounder CHQ WS2 Base Sounder Base Sounder Beacon Wall Sounder Sounderm CHQ DSC Sounder output module Inp mod CHQ_DIM Input module Zone mod CHQ_...

Страница 19: ...l smoke detector Thermo S90 Heat detector MCP S90 Manual Call Point Seg Segment Section of addresses with a maximum of 254 Hochiki detectors modules base sounders and a maximum of 126 Apollo detectors...

Страница 20: ...g counts how often this card initiated a network reconfiguration Comparing this counter with other devices gives information about a damaged network component 26 3 Display for analogue modem Modem Cal...

Страница 21: ...s devices Different protocol can be set to each serial interface of the FCP s menu 113 On all interfaces set to Modbus protocol connected devices will be scanned The address range for these devices is...

Страница 22: ...iving detector data bit 4 sending data to web server bit 5 given release to send bit 6 sending necessary bit 7 sending data The arrows in line 1 show receive and transmit activity signalises an occupi...

Страница 23: ...e Pre alarm alarm threshold depend on a the detector sensitivity which can be adjusted b the mode if the detector is a multi sensor Only for Hochiki ESP The push button Calib ration F3 can be used to...

Страница 24: ...isplay indicates that 4 spurs or 2 loops can be connected to this loop card Actually recognized are loop 1 and loop 2 29 1 FRP with FBC Software version S150A01 03 24V 1 OK 24V 2 Fault FBC OK Checksum...

Страница 25: ...ollo Discovery series has the ability to store data in the flash memory of the detector itself These data remains in memory even if the detector will be removed from the base The reading and transmitt...

Страница 26: ...taller menus After that the installer code is required To select sub menus you have the following possibilities Using the cursor keys and to mark the sub menu with the black background and then press...

Страница 27: ...uration software 3 To change the end user code Jump to Menu 04 4 To enter the diagnosis menu Jump to Menu 05 5 To enter the test mode That are the following functions Detector test Manual Controlling...

Страница 28: ...nstalled Jump to Menu 52 4 Revision means a One Man Test procedure to set smoke and heat detectors in alarm by using special test equipment During this procedure the FCP resets all alarms on the relev...

Страница 29: ...nu 68 3 To enter sub menu for system settings where some individual hardware and software features can be configured Jump to Menu 69 4 To enter sub menu for new scanning of addressable detectors Jump...

Страница 30: ...le IP settings Sprung in Menu 91 50 Detector test Status Zone 2 Normal Detector 3 Normal Alarm unset outputs inactive Cancel On set Example of detector test Detector not yet in alarm 0002 002 opt det...

Страница 31: ...sically address and confirm every line by OK b conventional zone Please type the Zone and as Detector type a 1 and confirm every line by OK The push button F4 set can be used to switch the function of...

Страница 32: ...the example left Press F2 Settings Jump to Menu 104 Menu 104 to assign on off functions to the outputs Press F3 Function Jump to Menu 105 Menu 105 to link the outputs with fixed standard functions of...

Страница 33: ...d power outputs switch off the internal buzzer etc Please type the loop number Seg and the output module s address as well as the input number and confirm every line by OK Press F4 Event Jump to Menu...

Страница 34: ...e configured analogue addressable or conventional The FCP Solution F1 has the ability not only to configure analogue addressable detectors but conventional detectors too That means you can assign to e...

Страница 35: ...n alarm coincidence means that at least 2 zones have to be in alarm condition to activate the main alarm passing to the fire brigade station If only one of the relating zones is in alarm there is only...

Страница 36: ...during one of the above described periods a main alarm will be activated immediately The response time can be 0 180 Sec The inspection time can be 1 7 Min Please confirm every line by OK and press F4...

Страница 37: ...tings 00 1 1 Selection 10 10 01 FBC settings 0 3 00 02 Transm Device settings 0 2 00 03 FCP cover contact 0 2 01 Cancel save If the German Fire Brigade Control Panel is connected to the Solution F1 th...

Страница 38: ...arameter printer controls the line feed of a connected printer 05 Fault reset 0 Automatically 1 by 06 Fault remind 0 30 Minutes or 0 no remind 07 Summer time switching 0 Automatically 1 Off 08 Detecto...

Страница 39: ...besides the individual texts of the detectors Even zones macro push buttons and timer programs will be deleted Before deleting there will appear the question Are you sure on the LC module which has t...

Страница 40: ...ancel Protocol Baud rate Configuring the interfaces The FCP offers 3 different serial interfaces RS 232 see wiring diagrams UART 2 can also be used as RS 485 interface For every interface a certain pr...

Страница 41: ...dem to answer an external phone call 2 Call accept off Disables the automatic call acceptance 3 Initialisation Initialises the modem with an ATZ command 4 Hang up Disconnects modem from telephone line...

Страница 42: ...n you can update the software of the main board The actual software version e g S040A12 00 x will be downloaded through RS232 interface by the NSC configuration software The protocol for UART 1 has to...

Страница 43: ...be done by a 6 digit code you can request form NSC By pressing F3 settings you will enter the configuration menu for every option ESPA 4 4 4 Menu 86 Modbus the Modbus slave address can be set SAA no s...

Страница 44: ...ionally to messages of the configured zones 90 Sections 0001 1000 RS485 device 1 Network ID 001 Zon 0001 Zon 0010 1 1 Selection 10 10 0001 Addr 01 No 001 Zon 0001 Zon 0010 0002 Addr 02 No 001 Zon 0011...

Страница 45: ...type the number of the OC output directly by using the keypad and confirm this by OK or by F4 Enter It is possible to operate several outputs simultaneously by using the from to function Underneath t...

Страница 46: ...tus as shown Active in the picture left side If the output is not active it is indicated as normal 104 Settings Output 001 On Off like Fire Output No On Off like sounders No On Off like Transm Dev No...

Страница 47: ...hese functions is used it is not possible to assign any other cause and effect events to the same output The sense is to create a parallel output to the listed outputs on the left side The function Sa...

Страница 48: ...n Fire Outputs off on the German Fire Brigade Control Panel If this parameter is set to yes and the push button is pressed the relating outputs are disabled On off like sounders output is controlled b...

Страница 49: ...nds 0 means no delay The functions are disabled by F2 No and the functions are enabled by F3 Yes After setting the parameters please press F4 Enter to save the configuration 109 Zones Seg 1 from addre...

Страница 50: ...es save Only for Hochiki ESP Table of the detector sensitivities Sens Opt ALG EN Heat ATG E Ion AIE E 0 2 0 50 0 20 V 1 2 5 55 0 24 V 2 3 0 EN54 60 A1S 0 28V EN54 3 3 5 66 0 32 V 4 4 0 72 0 36 V 5 4 5...

Страница 51: ...ix Modus 2 Fix Rate of rise 1 50 60 C A1R 14 K min 2 55 60 C A1 25 K min 3 60 A1S 78 C BR 16 K min 4 66 78 C B 25 K min 5 72 88 C CR 16 K min 6 78 BS 88 C C 25 K min 7 83 8 88 CS Only for Apollo Table...

Страница 52: ...program handles the day night mode switching and switching from one sensitivity mode to another one and vice versa Please confirm every line by OK and after finishing press save F4 to save the new co...

Страница 53: ...detectors on this line Press save F4 to save the new configuration If you have any doubts about these values for the requested detectors have a look into their data sheet If the FCP is shipped out by...

Страница 54: ...to 2048 Behind the number the cause and effect type is displayed The first line of the LC module shows the device which shall be configured at the moment because this has been selected before The las...

Страница 55: ...alarm 7 Fault power sup 4 Fault 8 Mains fault Cancel more Enter Page 2 Code 1 Alarm autom Det 5 Delay activated 2 Alarm MCP 6 Tran Dev active 3 KDB alarm 7 Tran Dev disabl 4 KDB unlocked 8 2 Alarm Ca...

Страница 56: ...also can be a detector on a not existing loop card Then activation of an input simulates message from a detector and all programmable features of that detector i e customer text or that zone i e alarm...

Страница 57: ...the control panel giving free access to the terminals for connecting the wires 5 Don t connect the panel to Mains AC yet Use the wiring diagrams for connecting loops conventional zones and sounders st...

Страница 58: ...of all components of fire control system as it is specified in the engineering documents Checking the documentation Document available yes no Repository Engineering order Final planning documents Upd...

Страница 59: ...om the cable resistance and the loop current which has to be measured later The resistance of the shielding also has to be written down in the following table Additionally this measurement guarantees...

Страница 60: ...r output cable The adaptation of open circuit and short circuit thresholds for the connected devices has to be done directly at the FCP Please go to Installer more F3 more F3 Power outputs Measurement...

Страница 61: ...0 Cancel Details Number of mounted detector modules correctly recognised Ok fault By pressing the Details key F3 the addresses of the modules can be checked Example Internal Modules 1 09 01 Loop card...

Страница 62: ...vices a list of these devices will be displayed This list will be visible each time the number of recognised detectors modules has changed after scanning the loops Therefore after first time initialis...

Страница 63: ...ently This is caused by the modulated protocol between the FCP and the loop devices For the measurement of the current the loop has to be separated on one side in the FCP and on the other side the cur...

Страница 64: ...cuments The following checklist describes the individual steps of the programming of the fire control panel Programming Menu topic Zones Alarm organisation Ok Detector configuration sensitivity mode o...

Страница 65: ...the installer level by functions test alarm or simulation Check display at FCP remote panels and printer Ok fault Ok fault Fault condition loop power outputs monitored inputs RS485 bus battery mains f...

Страница 66: ...Imax a Imax b Max Battery charge current 3 6 A Max load 180VA Version B01622 0x Max Output current 1 9 A Imax a Imax b Max Battery charge current 2 3 A The battery charge current can be limited in th...

Страница 67: ...ices Alarm activation equipment per FCP 1 Quiescent current of FCP without loop cards 90 mA Quiescent current loop card B01260 00 B01262 00 33 mA without detectors Quiescent current loop card B01270 0...

Страница 68: ...put voltage current 0 30 Volt 0 50 mA Power output voltage current 0 5 29 Volt 0 500 mA Relay voltage current 0 30 Volt 0 1 A Input voltage current 0 30 Volt 0 0 5 mA Input extinguishing system voltag...

Страница 69: ...7 8 Triggering of transmission devices for fire detections EN54 2 Cl 7 9 Output for the triggering of fire protection devices EN54 2 Cl 7 10 Fault surveillance of fire protection devices EN54 2 Cl 7...

Отзывы: