26
Internal Modules 01/09
>01 Loop card HOCHIKI ESP
02 Conventional detector card
03 -
04 -
05 -
06 -
Cancel Details
Internal Modules (PCBs): Details
The FCP displays the physically installed internal
modules (PCBs) with their addresses (1-9). These are
the addresses of the DIL switches on the PCBs.
Please select by the cursor keys the PCB which shall
be investigated more detailed and press F4
("Details")
Jump to Picture
29
26.2
Arcnet 1 Arcnet 2
Station ID : 001 | 001
Next ID : 002 | 002
Receive : OK | OK
Token seen : OK | OK
Send : OK | OK
Counter Reconfig.: 000 | 000
Cancel
Display of network adapters
Installed network adapters will be dispayed with
the following informations:
•
Station ID (1-255) is the network number of the
device (device no. set in the network
configuration Menu
81
).
•
Next ID (1-255) is the device number, to which
the token will be passed.
•
Receive (OK or F) shows, if the network card is
receiving data from another device.
•
Token seen (OK or F) shows, if the network card
has seen the token even if it doesn’t take part at
the network communication.
•
Send (OK or F) shows activity of the driver for
sending.
•
Counter Reconfig. counts, how often this card
initiated a network reconfiguration. Comparing
this counter with other devices gives information
about a damaged network component.
26.3
Display for analogue modem
Modem Call accept off
56000
P2109-V90
INSYS SmartSCM
FD
RCV56DPF-PLL L8
Cancel Details
Display for webserver module
Webserver
NSC Webserver V03.03
IP-Address
192.168.0.127
Netmask
255.255.255.0
Network
192.168.0.0#
Gateway
192.168.0.254#
CONNECT
Cancel
Modem data
If a telephone modem has been installed on the main
board, this menu displays different information,
dependant of the modem type (analogue, ISDN,
Ethernet). Here you see as an example the data of
the analogue modem.
Line 2: Product code
Line 3: Firmware version
Line 4: Modem version
Line 5: Country code (FD=Europe)
Line 6: Version of "Data pump"
In line 1 the actual modem status will be displayed.
The modem only accepts an incoming call, if the
automatic call acceptance has been activated in the
Details menu (same as Menu
80
) or in the installer
Menu
80
.
In the diagnosis menu for the webserver module the
firmware version will be displayed.
Below you see the network settings.
The '#' sign says that settings for "Network" and
"Gateway" are disabled. These parameters can be
activated by the configuration software easily. Then
the '#' sign won't be displayed anymore.
The "Network" setting usually won't be used.
"Gateway" is the address of the routers and has to be
activated if external access to the webserver should
be possible.