NSC Sicherheitstechnik GmbH
45/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
configuration file into the FCP.
With function key F3 ("UserInit") the User list in the
webserver module will be erased and set to the
delivery status.
After pressing F4 („save“) the changing will be stored
in flash memory and transferred to the webserver
module.
The modified settings will be valid only after hardware
reset of the webserver module.
For further information also see "B01380-00
Webserver User Manual ….pdf".
100
Manual control Status
from Output : 001 Active
to Output :
↓
+1
↑
-1 Selection ->+10 <--10
>001 Output 001 Main board
002 Output 002 Main board
003 Output 003 Main board
Cancel On Off Enter
Manual Control: internal OC Outputs
This menu to activate open collector outputs manually
by the user / installer to test their function.
Please select the OC output which shall be activated
by the cursor keys :
↑
,
↓
: Marker ">" one line up / one line down
<-, -> : Marker ">" 10 lines up / 10 lines down
or type the number of the OC output directly by using
the keypad and confirm this by "OK” or by F4
("Enter").
It is possible to operate several outputs
simultaneously by using the "from – to” function.
Underneath the grey line "Selection" the FCB
indicates where the selected outputs are. OC outputs
1 to 16 are on the main board, any further outputs are
on the additional loop cards :
OC outputs 01 – 16: on Main board
OC outputs 17 – 24: on loop card / convent. card 1
OC outputs 25 – 32: on loop card / convent. card 2
etc.
After confirming the output the last line of the LC
module changes and you can
activate the output by F2 ("On”)
deactivate the output by F3 ("Off”)
The activations can be checked on the LC module
because they will be displayed immediately or you
can check the status as shown "Active” in the picture
left side. If the output is not active it is indicated as
"normal”.
101
Manual Control Status
from relay : 001 Normal
to relay :
↓
+1
↑
-1 Selection ->+10 <--10
>001 Relay 001 Main board
002 Relay 002 Main board
003 Relay 003 Main board
Cancel On Off Enter
Manual Control: 4 internal Relays
This menu to activate the 4 internal relay outputs on
the main board manually by the user / installer to test
their function.
The way of operation is the same as in Menu
100
.