NSC Sicherheitstechnik GmbH
43/69
14.08.2013
Lange Wand 3
B01050 B01060 Operating Installation Manual Solution F1 20130814.doc
33719 Bielefeld
Version S040A13.08
software then calculates the thresholds for open
circuit and short circuit, dependant of the
tolerance, which also can be changed manually.
84
Loop parameters
Loop : 1
Open circuit : 9999 mV
Short circuit : 100 mA
Number of detector LEDs : 4
Cancel save
Loop parameters
In this menu the values for open circuit and short
circuit determined with the loop calculation
program (Excel sheet) can be entered.
Furthermore the number of detector LEDs,
which will be activated simultaneously on a loop,
can be specified in the range 3-12. This input is
important for the maximum alarm current, which
has influence on the maximum allowed cable
length and, as a consequence, to the
functionality of the system.
85
Options
1. ESPA 4.4.4
2. Modbus
3. VES
Cancel settings save
Options
Options are additional functions that are not part of
the standard software. The release of these options
has to be done by a 6 digit code you can request form
NSC.
By pressing F3 "settings" you will enter the
configuration menu for every option.
ESPA 4.4.4
->
Menu 86
Modbus
-> the Modbus slave
address can be set
SAA
-> no setting necessary
86
ESPA 4.4.4
Call address
: 0001
Beep Coding
: 1
Priority
: 1
Call Status
: 3
Text length
: 16
Timeout
: 010
Cancel save
ESPA 4.4.4 Settings
By ESPA 4.4.4 protocol all alarm messages and a
common fault message will be transferred to a
telephone server.
The first 4 parameters refer to the ESPA 4.4.4
specification.
For alarm messages the configured "Call address" will
be transmitted. As an option a common fault message
can be transmitted. This option can be activated in the
configuration software. The call address for common
fault message also will be set in the configuration
software.
Call address "5555" is a special case to realize
communication with a call system of company
"Winkel". With this Call address an additional text
"Feuer" will be transmitted prior the configured
customer text.
In the field "Text length" you can define, how many
characters of the detector text will be send to the
telephone serve. The input range is 16 up to 40.
The "Timeout" is a delay for a fault message in case
of communication error (10-255 sec).